User Manual

CHS Series Controller and Display Slant Fin Corp.
9
2.4 Advanced Setup
Figure 2-7 Advanced Setup (Menu) Screen
Advanced Setup menu screen, accessed by
selecting “Advanced Setup from the “i-Information”
screen, lists all of the configuration parameter groups.
Use the up and down (▲▼) buttons to navigate the
menu options; when the desired option is highlighted
select by pressing the “OK” button.
Login adjustment of many of the advanced settings
will prompt the user to login.
Table 2-5 Advanced Setup Menu Options
Name
Description
Reference:
CH Config
Edit Central Heat settings; CH1 heat input.
Section 2.4.1
DHW Config
Edit Domestic Hot Water settings.
Section 2.4.2
Lead Lag Config
Edit Lead-Lag Master and Slave settings; CH2 (LL) heat input.
Section 2.4.3
System Config
Edit temperature units, anti-short-cycle time, alarm silence time.
Section 2.4.4
Modulation Config
Edit burner modulation settings.
Section 2.4.5
Delta T Limits
Edit delay time for delta-t limit.
Section 2.4.6
T-rise Limits
Edit delay time for T-rise limit.
Section 2.4.6
Frost Protection Config
Enable/disable CH, DHW and LL frost protection
Section 2.4.7
Burner Timings & Rates
Read only, for information only.
Section 2.4.8
Burner Control Ignition
Read only, for information only.
Section 2.4.9
CH Config
DHW Config
Lead Lag Config
System Config
Modulation Config
Delta T Limits
T-rise Limits
Frost Protection Config
Burner Control Timings & Rates
Burner Control Ignition
Advanced Setup