8 EH-M2-40 Boiler Operation and Installation Instructions
Basic Monitron II and Minitron M3 Setup
Dual Temperatures are Fahrenheit (Celsius)
Field Entry Example for Mode 4 or Mode 5
Field Entry Baseboard System
Low Temp
System
Note
Mode 4 or 5 4 or 5 4 = Parallel Piping, 5 = Primary/Secondary Piping
STGMODE PID P P
BOIL TARGET 180(82) 180(82) 180(82) This is for DHW setpoint demand - if used
OUTDR START 70(21) 70(21) 70(21)
OUTDR DSGN* -10(-23) -10(-23) -10(-23) May be -20(-29) or -30F(-34) depending on area design temp.
BOIL START 70(21) 70(21) 70(21) This is used in the calculation of slope
BOIL DSGN 180(82) 180(82) 130(54) Radiant - 130(54) Wet, 140(60) or 150F(66) for Dry system
BOIL OUT MAX 182(83) 182(83) 150(66) Default 182(83) - Use "FACTORY" Dip Switch to Adjust - DO NOT EXCEED THIS MAX
BOIL MAX 170(77)
170(77)
130(54)
Default 180(82) - Use "FACTORY" Dip Switch to Adjust. Set same as BOIL DSGN
BOIL MIN 140(60)
140(60) 80(27)
Default 140(60) - Use "FACTORY" Dip Switch to Adjust.
Note:Some heating equipment may require a minimum water temperature - ie fan coils
DLY No Entry
Not valid for Electric Boiler application
BOIL MASS 1
N/A N/A
STG DLY Au if PID in STGMODE
N/A N/A Minimum time between firing stages
DIFF Au if PID in STGMODE
2(1) 2(1) 1/2 differential around target temp
STG DIFF
4(2) 4(2) Temperature drop at which next stage turns on
ON DLY
1:00 1:00 Time before turning on next stage
OFF DLY
0:30 0:30 Time before turning off next stage
MIN ON
0:30 0:30 Minimum time stage is on before allowed to go off
MIN OFF
0:30 0:30 Minimum time stage is off before allowed to come on
PUMP DELAY Off Off Off
WWSD 65(18)
0˚ F F or C
Set the "MODE" to 1 or 2 if an outdoor Sensor is not used (1 = parallel piping, 2 = primary/secondary piping)
Caution:
“Factory” position on dip switch has to be returned to “installer” position to prevent unauthorized changes to factory settings.
*Local design input may vary from the example shown. Be sure to use design inputs for your geographical location.
EXAMPLE SETTINGS MAY VARY ACCORDING TO ACTUAL DESIGN REQUIREMENTS.