Installation Guide

6
BATTERY REPLACEMENT PROCEDURE
(Step 7A on Page 4)
Sloan OPTIMA Plus
®
EBF-85 and EBF-187 Battery Powered, Sensor
Activated Lavatory faucet models are furnished with four (4) Duracell C-
size Alkaline batteries that provide up to 2 years of operation (at 8000
cycles per month). When the batteries are low and need to be replaced, the
EBF-85 and EBF-187 will signal you. When 256 cycles remain in the unit,
the faucet will BEEP each time it is activated. At this point we recommend
battery replacement. Sloan Valve recommends the use of Duracell MN-
1400 C-size batteries.
To Replace Batteries:
Note: Water supply to the faucet does not need to be turned off when
replacing batteries.
Loosen security set screw on the Coupling Ring with a 0.05” hex wrench.
Unscrew Battery Compartment Coupling Ring. Remove Battery
Compartment. To ensure proper operation, remove old batteries and insert
four (4) new C-size Alkaline batteries. Check that the orientation of each
battery matches the positive (+) and negative (-) symbols shown at the
bottom of the Battery Compartment. Reattach the Battery Compartment to
the Valve Module by aligning the arrow on the Battery Compartment with
the arrow on the solid tab of the Solenoid Valve Module. Secure by
tightening Battery Compartment Coupling Ring. To deter unauthorized
removal of batteries, use a 0.05” hex wrench to tighten the security set
screw on the Coupling Ring.
Upon installation of the batteries, the EBF-85 and EBF-187 faucet will begin
a new self-calibration procedure (see START UP MODE).
SOLENOID SCREEN FILTER CLEANING
PROCEDURE
A
Unscrew the Filter Cap and remove it from the Solenoid Valve
Housing and carefully pull the Screen Filter with attached rubber
seals out from the Solenoid Valve Housing.
B
Clean the Screen Filter using fresh tap water only. If necessary,
use a small brush to clean. Use caution while cleaning to prevent
damage to the Solenoid Screen Filter. If any Filter components are
damaged, order Filter Replacement Kit EBF-1004-A.
C
Carefully replace the Screen Filter into the groove of the Solenoid
Valve Housing. Examine the Filter Cap O-ring for wear or damage;
replace if necessary.
D
If necessary,
lubricate the Filter
Cap O-ring with
water to keep it in
place in the
groove of the
Filter Cap. Screw
the Filter Cap into
the Solenoid
Valve Housing.
E
Turn on the water supply at the supply stop(s). Activate the faucet
to purge any air from the system lines. Check for leaks and repair
as necessary.
SOLENOID VALVE
HOUSING
SCREEN FILTER
FILTER CAP O-RING
FILTER CAP
IF FILTER COMPONENTS
ARE DAMAGED, ORDER
FILTER REPLACEMENT KIT
— EBF-1004-A
Note: Before cleaning the Screen Filter, turn off the water supply at the
supply stop(s) and activate the faucet to relieve any pressure in the
system.