Installation Sheet

GANG
SCREWS
SLOAN VALVE COMPANY
U.S.A.
(24 VAC IN)
CONNECT TO LISTED
CLASS 2 SOURCE
(TO VALVE)
10 W MAX
CRITICAL DIMENSION
MUST BE WITHIN ± 1/8” (3 mm)
OPTIMA SYSTEMS
Electrical Box Rough-In Template for
Sensor Operated Exposed Water Closet Flushometers.
WATER CLOSET
FLUSHOMETER
TEMPLATE
WIRING DIAGRAM
Models: Royal,Regal/Sloan & Crown 110 ES-S /111 ES-S
(DO NOT use this template for other Model ES-S Flushometers)
CUT ALONG DOTTED LINES
Note: A maximum of ten (10) Sensor Flushometer units can operate from one
(1) Sloan EL-154 transformer. Class II UL Listed, 48 VA (min.) at 24 VAC,
plate mounted.
WIRING NOTES
Be certain power is OFF to prevent
damage to electrical components.
Connect sensor to transformer and
solenoid coil EXACTLY as shown in
Wiring Diagram.
Connect the 24 volt source lead to
terminal labeled “24 VAC IN” of new
sensor.
Connect solenoid lead to terminal
labeled “TO VALVE” of new sensor.
Connect remaining solenoid lead to
remaining 24 volt source lead.
Connect override button parallel to
the EL-1500-L sensor. Use 18
gauge wire between override button
terminals and the connection of the
EL-1500-L sensor.
This template will serve as a guide when
Roughing-In the Electrical Boxes required for a
Sloan OPTIMA Flushometer. If further assistance is
needed contact your nearest Sloan Representative
Office.
Refer to the OPTIMA Flushometer Installation
Instructions for directions to install and operate the
Valve.
120 VAC
24 VAC
GND
UNIT #1
UNIT #2
THRU #10
(IF USED)
IMPORTANT: Early Models of the Sensor were made with four (4) Wire
Leads. When replacing a four (4) Wire EL-150-L Sensor with a three
(3) Wire EL-150-L Sensor the Black Lead replaces the
Blue Lead, the Red Lead replaces the Yellow Lead and the White Lead
combines and replaces the Brown & Red Leads.
SLOAN • 10500 SEYMOUR AVENUE • FRANKLIN PARK, IL 60131
Phone: 800.800.982.5839 • Fax: 1-847-671-4380 • sloanvalve.com
Copyright © 2015 Sloan Valve Company Template — Rev. 1 (10/15) Code No. 0816157
24 VAC COIL
24 VAC COIL
SOLENOID
GROUND
WIRE
SOLENOID
GROUND
WIRE
COIL WIRE
COIL WIRE
EL-1500-L SENSOR
EL-1500-L SENSOR
SENSOR
“TO VALVE”
CONNECTION
“24 VAC IN”
CONNECTION
CUT ALONG DOTTED LINES
4” X 4” X 2-1/2” DEEP
ELECTRICAL JUNCTION BOX
(102 mm X 102 mm X 63 mm)
WATER SUPPLY
1” (DN 25 mm) I.P.S.
C/L
OF
ELECTRICAL
BOX
SENSOR LOCATION AND POSITIONING
IS CRITICAL!
Failure to properly position the electrical boxes to
the plumbing rough-in will result in improper
installation and impair product performance. All
tradesmen (plumbers, electricians, tile setters, etc.)
involved with the installation of this product must
coordinate their work to assure proper product
installation.
Note: When installing the valve with the EL-485-A positioning
and support kit, refer to the instructions packaged with the
EL-485-A. DO NOT USE THIS PAPER TEMPLATE.
IMPORTANT!
DO NOT use this template for other Model
ES-S Flushometers.
TOP OF FIXTURE
HOW TO USE TEMPLATE
Cut out Supply and Box openings (dotted lines).
Place template over water supply rough-in.
Align “C/L of Fixture” on template with actual Center Line of Fixture.
Mount Electrical Box according to opening in template.
POSITION OF SENSOR BOX CAN BE
RAISED OR LOWERED 1” (25 mm) IF IN
CONFLICT WITH HANDICAP GRAB BARS
OVERRIDE BUTTON
2 ¾”
(70 mm)
CUT ALONG DOTTED LINES
CUT ALONG DOTTED LINES
CUT ALONG DOTTED LINES
CUT ALONG DOTTED LINES
CUT ALONG DOTTED LINES
CUT ALONG DOTTED LINES
IMPORTANT: MOUNT GANG SCREWS OF PLASTER
RING OR GANGBOX WITH SCREWS ON THE SIDES
19” (482 mm)
FROM TOP
OF FIXTURE
2-3/4” (70 mm)
4-3/4” (121 mm)
SLOAN ADJUSTABLE TAIL
ALLOWS ± 1/2” (13 mm) VARIATION
C/L
OF
FIXTURE
1-1/2” (38 mm)
CRITICAL DIMENSION MUST
BE WITHIN ± 1/8” (3 mm)
11-1/2” (292 mm)
FROM TOP
OF FIXTURE
2 ¼”
(70 mm)
4 ¾”
(121 mm)
19”
(482 mm)
11½”
(292 mm)
1½”
(38 mm)
C/L OF
ELECTRICAL
BOX