5 Mounting
SMA Solar Technology AG
Installation Manual SBSxx-US-10-IA-xx-12 27
Prescribed clearances in accordance with the
National Electrical Code
®
or
Canadian Electrical Code
®
CSA C22.1
Under certain conditions, the National Electrical Code
®
or the Canadian Electrical Code
®
CSA C22.1 specify greater clearances.
• Ensure that the prescribed clearances in accordance with the National Electrical Code
®
or Canadian Electrical Code
®
CSA C22.1 are adhered to.
☐ Maintain the recommended clearances to walls as well as to other inverters or objects.
☐ If multiple inverters are mounted in areas with high ambient temperatures, increase the
clearances between the inverters and ensure sufficient fresh-air supply.
Figure 9 : Recommended clearances(Dimensions in mm (in))
5.2 Mounting the Inverter
Additionally required mounting material (not included in the scope of delivery):
☐ Three screws suitable for the support surface (diameter: 8mm (5/16in))
☐ Three washers suitable for the screws
☐ Where necessary, 3 screw anchors suitable for the support surface and the screws
☐ To secure the inverter against theft: one padlock suitable for outdoor use
☐ Padlock dimensions:
– Diameter of the shackle: 8mm to 10mm (0.31in to 0.39in)
– Width of the shackle (inner dimension): 30mm to 40mm (1.18in to 1.57in)
– Height of the shackle (inner dimension): 30mm to 40mm (1.18in to 1.57in)