6 Electrical Connection
SMA Solar Technology AG
Installation ManualSBSxx-US-10-IA-xx-1248
Procedure:
The battery limited to a charging/discharging current of 20A must be connected to the terminal
blocks of the fuse holder A/B.
The battery limited to a charging/discharging current of 10A must be connected to the terminal
blocks of the fuse holder C.
Figure 12 : Overview for connection of two batteries with varying charging/discharging current limits
Connection of two batteries with a charging/discharging current limit of 10A
each
The DC terminals A and B of the inverter are connected in parallel as standard. The parallely
connected DC terminal A/B limits the charging/discharging current to 20A and the DC terminal C
to 10A.
If you want to connect two batteries with a charging/discharging current limit of 10A each,
proceed as follows: First, remove the parallel connection of the DC terminal A/B. Then replace the
25A fuses of the fuse holder A/B with 15A fuses. When the parallel connection has been
removed and the fuses replaced, the DC terminal A/B is able to limit the charging/discharging
current to 10A.
Additionally required material (not included in the scope of delivery):
☐ One cylindrical fuse link (15A, 10x38mm, ≥ 600VDC)
☐ DC conductor for connection to fuse holders The requirements in terms of the DC conductors
used for connection to the fuse holders must be met (see Section6.8.2 "Requirements for the
DC Connection", page53).