User and installation manual

10 Technical Data
SMA Solar Technology AG
Installation Manual SBSxx-US-10-IA-xx-12 71
10.1.2 SunnyBoyStorage 6.0-US
AC connection
SBS6.0-US-10
Rated power 6000W
Maximum apparent AC power 6000VA
Rated grid voltage 240V
AC voltage range 211V to 264V
Nominal AC current 25A
Maximum output current during stand-alone
mode
32A
Total harmonic factor of output current <4%
Maximum residual output current 198Apeak
Duration of the maximum residual output current 33ms
Line synchronization characteristics/inrush cur-
rent
Method 2/18.5A
Rated power frequency 60 Hz
Limits of accuracy of voltage measurement 2% of the AC voltage
Limits of accuracy of frequency measurement ±0.1Hz
Limits of accuracy of time measurement at nomi-
nal trip time
± 0.1 %
Limits of accuracy of current measurement 1% of the AC current
Limits of accuracy of power (active/reactive)
measurement
5% of the nominal AC power
Limits of accuracy of power factor measurement 0.01
Limits of accuracy of time measurement 0.001s
Operating range at AC power frequency 60Hz 59.3Hz to 60.5Hz
Output power at +60°C (+140°F) > 4000W
Power factor at rated power 1
Range of the displacement power factor (ad-
justable)
0.8
overexcited
to 0.8
underexcited
Feed-in phases 1
Phase connection 2
Overvoltage category in accordance with
UL1741
IV
ENGLISH