User and installation manual

10 Technical Data
SMA Solar Technology AG
Installation ManualSBSxx-US-10-IA-xx-1272
DC connection for battery
Maximum DC voltage 600V
Voltage range* 100V to 550V
DC rated voltage 360V
Maximum DC current 3 x 10A
Maximum short-circuit current 40A
Battery type** Li-ion
Overvoltage category in accordance with
IEC60664-1
III
* The charging and discharging voltage of the connected batteries must be in the range of 220V and
500V in order to make optimum use of the power of the inverter
** Only use batteries approved by SMA Solar Technology AG (see list of approved batteries at
www.SMA-Solar.com)
Efficiency
SBS6.0-US-10
Maximum efficiency, η
max
97.5%
CEC efficiency, η
CEC
96.5 %
10.2 AC Output, Secure Power Supply Operation
Maximum AC power 2000W
Nominal AC voltage 120V
AC voltage range 109V to 132V
Maximum output current 16A
Minimum load 1W
10.3 Triggering Thresholds and Tripping Time
Rated power fre-
quency
Triggering threshold Triggering frequency Tripping time
60 Hz > 60.5 Hz 60.45 Hz to 60.55 Hz max. 0.1602 s
< 57Hz to 59.8Hz
(Standard: 59.3Hz)
56.95Hz to 59.85Hz
(Standard: 59.25Hz
to 59.35Hz)
Adjustable: 0.16s to
300s
(Standard: max.
0.1602s)
< 57.0 Hz 56.95 Hz to 57.05 Hz max. 0.1602s
ENGLISH