Troubleshooting Sunny Beam Manual
44
Inverter Detection
All Inverters are not Detected
If after running the detection routine, one or more of the inverters are not detected, try the
following:
• Check that the Sunny Beam is set for the correct Group (channel)
• Check the DIP switch on the communication board in the Sunny Boy to make sure it is set
for the correct Group (channel)
• Move the Sunny Beam so that it is closer to the Sunny Boys
• Make sure that the Sunny Beam is approximately 10 feet from the Sunny Boys while
detecting.
NOTE: Though this may sound counterintuitive, it is possible for the Sunny Beam
to have difficulty communicating if it is too close to the Sunny Boy antenna. This is
caused by the overloading of the receivers in both units. To prevent this, try to keep
the Sunny Beam and Sunny Boys at least 10 feet apart.