Installation Guide

Table Of Contents
5 Mounting
SMA Solar Technology AG
Installation Manual SBxx-1SP-US-41-IA-xx-10 23
5 Mounting
5.1 Requirements for Mounting
Requirements for the Mounting Location:
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not mount the product in areas containing highly flammable materials or gases.
Do not mount the product in potentially explosive atmospheres.
A solid support surface must be available (e.g. concrete or masonry, free-standing
constructions). When mounted on drywall or similar materials, the inverter emits audible
vibrations during operation which could be perceived as annoying.
The installation site can be exposed to direct solar irradiation. There is, however, the possibility
that the product reduces its power output to avoid overheating due to high temperatures.
When using the SMACellularLTEModemKit, the installation site should not be located in the
basement. The data transmission during basement installation can be restricted due to an
insufficient connection quality.
The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
The DC load-break switch of the product must always be freely accessible.
All ambient conditions must be met (see Section10, page65).
Permitted and prohibited mounting positions:
The product may only be mounted in a permitted position. This will ensure that no moisture can
penetrate the product.
The product should be mounted in such way that display messages and LED signals can be
read without difficulty.
15°
Figure 3 : Permitted and prohibited mounting positions
Do not mount multiple inverters directly above one another.