Sunny Tripower Installation Manual

SMA America, LLC 6 Electrical Connection
Installation Manual CU600-1000US-IA-en-10 27
6.2 Overview of the Connection Area
6.2.1 Enclosure Openings
Figure 9: Enclosure openings of the Connection Unit
Electrical installations
All electrical installations must be made in accordance with the local electrical standards and
the National Electrical Code
®
ANSI/NFPA70 or the Canadian Electrical Code
®.
CSA C22.1.
Use only +194°F (+90°C) copper wire for all DC wiring connections to the screw
terminals between the PV modules and the Connection Unit and between the Connection
Unit and the inverter.
The DC input and output circuits are isolated from the enclosure and that system grounding,
if required by Section 250 of the
National Electrical Code
®
, ANSI/NFPA 70, is the
responsibility of the installer.
Make sure that no damaged cables are being used.
Item Designation
A Output opening in the enclosure for connecting the conduits
(diameter: 1
23
64
in. (34.5 mm) to 1
3
8
in. (34.7 mm))
B Input opening in the enclosure with filler plugs for connecting the conduits
(diameter: 1
3
32
in. (27.8 mm) to 1
7
64
in. (28.0 mm))