2. Minimum RMS AC of the output voltage for an individual device. Minimum voltage injection per phase of a SmartValve
System consisting of n devices per phase is the Minimum Injection Voltage of a single device as the other n-1 devices per
phase can be operated in Monitoring Mode.
3. The value shown is for the standard device. When equipped with the Enhanced-Availability package, the minimum injection
voltage for an individual device is 57 V RMS.
4. The value shown is for an individual device provided the line current is at least 750 A RMS. For a SmartValve System with n
devices in series per phase, the maximum ramp rate of the set is n times the Maximum Ramp Rate.
5. In Monitoring Mode, the SmartValve is bypassed and does not inject voltage, while telemetry data is still transmitted. In
Injection Mode, the SmartValve injects voltage in series with the line and telemetry data is transmitted.
6. The standard device fulfills this rating at 104°F (40°C), 1000 W/m
2
of solar radiation and 1000 m elevation. Ratings at other
environmental conditions (e.g. 122°F (50°C)) or durations (e.g. 15 minutes) are available upon request.
7. The device can operate in a de-rated mode at temperatures above 104°F (40°C) up to e.g. 122°F (50°C). Ratings for these
conditions are available upon request.
8. For the fiber-optic package, all radios are disabled via hardware modification.
9. Applicable for line currents between 1440 A RMS and 2160 A RMS.
About Smart Wires
Smart Wires is a global power technology company advancing the delivery of affordable, clean electricity worldwide. With
our innovative technology and advanced analytics, we maximize the grid’s capacity. This means more renewables, at a
lower cost and with less disruption to communities and the environment. Smart Wires is headquartered in North Carolina,
with European headquarters in Dublin, Ireland, and a global workforce of 200 professionals spread across four continents.
Our team collaborates with our customers to achieve their strategic objectives and help them face an uncertain energy
future with flexible, high-impact solutions.
While Smart Wires strives to make the content of its marketing materials as timely and accurate as possible,
Smart Wires makes no claims, promises, or guarantees about the accuracy, completeness, or adequacy of, and
expressly disclaims liability for errors and omissions in, such materials. No warranty of any kind, implied,
expressed, or statutory, including but not limited to the warranties of non-infringement of third-party rights,
title, merchantability, and fitness for a particular purpose, is given with respect to the content of these
marketing materials. © Copyright 2021, Smart Wires Inc. All rights reserved.
Smart Wires Inc.
www.smartwires.com
D001259 Rev B
Regulatory Compliance User Notice:
FCC:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
ISED:
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development
Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
This device may not cause interference.
This device must accept any interference, including interference that may cause undesired operation of the device.
L’émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d’Innovation, Sciences et
Développement économique Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux
deux conditions suivantes :
L’appareil ne doit pas produire de brouillage;
L’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le
fonctionnement.
CAUTION:
Changes or modifications not expressly approved by the party responsible for compliance could void the user's
authority to operate the equipment.
NOTES:
*. 866 Mhz. operation is not supported in this version.