Installation Guide
2 
2 
PRE-INSTALLATION SUBFLOOR REQUIREMENTS 
Note: All subfloors must be flat to within 3/16” in 10’ or 1/8” in 6’ 
Wood Subfloors 
Do not install material over wood subfloors that lay directly on concrete or over dimensional lumber or plywood used over 
concrete. Refer to ASTM F1482 for panel underlayment recommendations. 
Do not apply sheet plastic over wood subfloors. 
Basements and crawl spaces must be dry. Use of a 6 mil black polyethylene is required to cover 100% of the crawl space earth. 
Crawl space clearance from ground to underside of joist is to be no less than 18” and perimeter vent spacing should be equal to 
1.5% of the total square footage of the crawl space area to provide cross ventilation. Where necessary, local regulations prevail. 
All other subfloors - Plywood, OSB, particleboard, chipboard, wafer board, etc. must be structurally sound and must be installed 
following their manufacturer’s recommendations. Local building codes may only establish minimum requirements of the flooring 
system and may not provide adequate rigidity and support for proper installation and performance. If needed add an additional 
layer of APA rated underlayment, fasten and secure according to the underlayment manufacturer’s recommendations.   
Resilient flooring is not recommended directly over fire-retardant treated plywood or preservative treated plywood. An additional 
layer of APA rated 1/4" thick underlayment should be installed. 
Concrete Subfloors  
Floors shall be smooth, permanently dry, clean, and free all foreign material such as dust, wax, solvents, paint, grease, oil s, and old 
adhesive residue. The surface must be hard and dense, and free from powder or flaking. 
New concrete slabs must be dry. Maximum moisture level per CaCl test method is 5 lbs. per 1000 in 24 hr. Maximum level for 
ASTM 2170 In-situ Relative humidity test method - 85%. 
Do no install over concrete with a history of high moisture or hydrostatic conditions.  
Ph level of concrete should be between 7-10 
The final responsibility for determining if the concrete is dry enough for installation of the flooring lies with the floor covering 
installer. 
  WARNING! DO NOT SAND, DRY SWEEP, DRY SCRAPE, DRILL, SAW, BEADBLAST OR MECHANICALLY CHIP OR PULVERIZE EXISTING 
RESILIENT FLOORING, BACKING, LINING FELT, ASPHALTIC “CUTBACK” ADHESIVES OR OTHER ADHESIVES. 
These products may contain either asbestos fibers and/or crystalline silica. Avoid creating dust. Inhalation of such dust is a cancer and respiratory 
tract hazard. Smoking by individuals exposed to asbestos fibers greatly increases the risk of serious bodily harm. Unless positively certain that the 
product is a non-asbestos-containing material, you must presume it contains asbestos. Regulations may require that the material be tested to 
determine asbestos content and may govern the removal and disposal of material. See current edition of the Resilient Floor Covering Institute 
(RFCI) publication Recommended Work Practices for Removal of Resilient Floor Coverings for detailed information and instructions on removing all 
resilient covering structures. For current information go to www.rfci.com 
Existing Floor Coverings 
  SMARTCORE® Naturals flooring can be installed over most existing hard–surface floor coverings (including ceramic tile) provided that the 
existing floor surface is clean, flat dry and structurally sound. 
  Existing sheet vinyl floors should not be heavily cushioned and not exceed more than one layer in thickness. 
  Installation is NOT allowed over any type of carpet. 
  Do NOT install over wood subfloor or wood floors adhered to concrete. 
Ceramic tile. 
  Never use solvents or citrus adhesive removers to remove old adhesive residue. Solvent residue left in and on the subfloor may affect the new 
floor covering. 
STARTING YOUR 
INST
ALLA
TION
Because houses 
and buildings,  as well as 
adjacent hardwood 
or 
laminate 
floors, 
expand 
and 
contract, 
USFloors 
recommends 
leaving  a ¼” 
expansion 
gap 
between 
the 
perimeter 
walls  and  any 
adjacent hardwood 
floor
.
For floating installations an underlayment is generally not required. However, if you prefer an even quieter installation you can 
include an underlayment approved for resilient products. 
Note:
 Larger rooms require additional expansion space. Add 1/16” to the width of the expansion space for every 3’ the room 
extends beyond 25’. Dimensions exceeding 40’in length or width – it is recommended to use a T-Molding for proper expansion. 
Work  from 
several 
open boxes
of flooring  and  “dry lay”  the floor 
before permanently 
laying  the floor. This will allow  you  to 
select 
varying 
textures, 
colors, and 
sheens, 
and to 
arrange them 
in a 
harmonious pattern. Remember, 
it is the 
inst
aller
’
s
responsibility 
to determine 
the 
expectations 
of what the finished floor will look  like with the end user first  and then to  cull out 
pieces 
that do 
not 
meet those expectations. 





