AIN16-M01 ANALOG INTEGRATED MODULE USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO.,LTD.
AIN16-M01 Analog Integrated Module User Manual Chinese trademark English trademark SmartGen — make your generator smart SMARTGEN(ZHENGZHOU) TECHNOLOGY CO., LTD. No. 28 Jinsuo Road Zhengzhou City P. R. China Tel: +86-371-67988888 +86-371-67981888 +86-371-67991553 +86-371-67992951 +86-371-67981000 (overseas) Fax: 0086-371-67992952 Web: http://www.smartgen.com.cn http://www.smartgen.cn Email: sales@smartgen.cn All rights reserved.
AIN16-M01 Analog Integrated Module User Manual This user manual only suits for AIN16-M01 Analog Integrated Module. Notation Clarification as follows, Symbol NOTE Instruction Highlights an essential element of a procedure to ensure correctness. Indicates a procedure or practice, which, if not strictly observed, could result in CAUTION damage or destruction of equipment. Indicates a procedure or practice, which could result in injury to personnel or loss of life WARNING if not followed correctly.
AIN16-M01 Analog Integrated Module User Manual CONTENTS 1 OVERVIEW ......................................................................................................................................... 5 2 PERFORMANCE AND CHARACTERISTICS .................................................................................... 5 3 TECHNICAL PARAMETERS .............................................................................................................. 5 4 CONNECTION ...........................
AIN16-M01 Analog Integrated Module User Manual 1 OVERVIEW AIN16-M01 analog integrated module contains 8 PT100 sensor input channels, 3 speed input channels, 4 4~20mA output channels and one 4~20mA input channel. The data are transmitted to the HMC9000 controller for processing via CANBUS port, then HMC9000 transfers 4~20mA data back into AIN16-M01 module via CANBUS port and AIN16-M01 outputs corresponding 4~20mA signals. Values can be set for each sensor via HMC9000 controller as demands.
AIN16-M01 Analog Integrated Module User Manual 4 CONNECTION No. 1 2 BB+ Function 3 SCR 4 CAN(H) 0.5mm2 CAN(L) 6 120Ω Terminal Resistor 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 MP1 MP2 MP3 AOUT1 AOUT2 AOUT3 AOUT4 CIN1 Description DC power supply negative input. DC power supply positive input. CANBUS shielded wire, with single end earthed. 5 7 Cable Size 1.0mm2 1.
AIN16-M01 Analog Integrated Module User Manual 23 24 C PTIN1 B 25 A 26 C 27 PTIN2 B 28 A 29 C 30 PTIN3 B 31 A 32 C 33 PTIN4 B 34 A 35 C 36 PTIN5 B 37 A 38 C 39 PTIN6 B 40 A 41 C 42 PTIN7 B 43 A 44 C 45 PTIN8 46 B 0.5mm2 0.5mm2 0.5mm2 0.5mm2 PT100 sensors are three-wire system terminals, and C terminal stands for common port. A and B terminals are amphenol connectors. 0.5mm2 0.5mm2 0.5mm2 0.
AIN16-M01 Analog Integrated Module User Manual 5 PROTECTION All data can be protected via HMC9000 controller. HMC9000 can connect to two AIN16-M01 modules at the same time and users can select module address via dial switch. Following parameters can be set via HMC9000: 1) AIN16-M01 module enable: HMC9000 can communicate with the module and collect the data; 2) Each of sensor’s alarm threshold and alarm are enabled; AIN16-M01 can collect data only and all alarms are initiated by HMC9000 controller.
AIN16-M01 Analog Integrated Module User Manual 5.2 SHUTDOWN ALARM Shutdown types are as follows, No.
AIN16-M01 Analog Integrated Module User Manual 5.4 PTIN1~PTIN8 AND CIN1 SETTINGS No.
AIN16-M01 Analog Integrated Module User Manual 5.5 MP1~MP3 SETTINGS No. Items Contents Remarks 0:Disable 1. Sensor Enable 2. Teeth Number 3. High Shutdown Enable 4. High Shutdown Value (0-6000) 5. High Shutdown Delay (0-3600)s 6. High Warn Enable 7. High Warn Value (0-6000) 8. High Warn Delay (0-3600)s 1:Enable (1-300) 0:Enable 1:Disable 0:Enable 1:Disable 5.6 AOUT1~ AOUT4 SETTINGS No.
AIN16-M01 Analog Integrated Module User Manual 6 ELECTRICAL CONNECTIONS AIN16-M01Electrical connection diagram is as follows, HMC9000 with two AIN16-M01 modules connection diagram is as follows, 7 INSTALLATION AIN16-M01 Analog Integrated Module 2017-03-17 Version 1.
AIN16-M01 Analog Integrated Module User Manual 8 TROUBLE SHOOTING Problem Possible Solution Check batteries; Controller no response with power. Check controller connection wirings; Check DC fuse. CANBUS communication failure Check if CANBUS wires are connected in the opposite way. AIN16-M01 Analog Integrated Module 2017-03-17 Version 1.