5.4 PTIN1~PTIN8 AND CIN1 SETTINGS
No.
Items
Contents
Remarks
1
Sensor types
0:Not Used
1:Oil Pressure Sensor
2:Temperature Sensor
2
Sensor Curve
0:PT100
1:4~20mA
3
Alarm Speed
(0-200)%
4
Range (current type)
(0-6000)kpa
5
High Shutdown Enable
0:Enable
1:Disable
6
High Shutdown Value
(0-6000)
7
High Shutdown Delay
(0-3600)s
8
Low Shutdown Enable
0:Enable
1:Disable
9
Low Shutdown Value
(0-6000)
10
Low Shutdown Delay
(0-3600)s
11
High Warn Enable
0:Enable
1:Disable
12
High Warn Value
(0-6000)
13
High Return Value
(0-6000)
14
High Warn Delay
(0-3600)s
15
Low Warn Enable
0:Enable
1:Disable
16
Low Warn Value
(0-6000)
17
Low Return Value
(0-6000)
18
Low Warn Delay
(0-3600)s
19
User-defined string
User can reset the sensors’ names which are displayed on
HMC9000 LCD. e.g. rename sensor 1 as Temperature Exhaust
sensor. User-defined string can be edited via HMC9000 PC
software only.