4 CONNECTION
Function
Cable Size
Description
B-
1.0mm
2
DC power supply negative input.
B+
1.0mm
2
DC power supply positive input.
SCR
0.5mm
2
CANBUS shielded wire, with single end earthed.
CAN(H)
A CANBUS port which communicate with
HMC9000 controller.
CAN(L)
120Ω Terminal Resistor
Short out 5 and 6 terminals if 120Ω terminal resistor
is needed.
MP1
-
0.5mm
2
Connect with speed sensor(shielded wire is
recommended). Speed sensor input (-), B- has been
connected in the controller.
+
MP2
-
0.5mm
2
+
MP3
-
0.5mm
2
+
AOUT1
COM1
0.5mm
2
4~20mA output common port
mAOUTPUT1
4~20mA output port
AOUT2
COM2
0.5mm
2
4~20mA output common port
mAOUTPUT2
4~20mA output port
AOUT3
COM3
0.5mm
2
4~20mA output common port
mAOUTPUT3
4~20mA output port
AOUT4
COM4
0.5mm
2
4~20mA output common port
mAOUTPUT4
Sensor terminal
CIN1
COM(B+)
0.5mm
2
4~20mA analog input.
B+ input (supply power for pressure transmitter)
mA