User Manual
AIN16-M01 Analog Integrated Module User Manual
AIN16-M01 Analog Integrated Module 2017-03-17 Version 1.1 Page 6 of 13
4 CONNECTION
No.
Function
Cable Size
Description
1
B-
1.0mm
2
DC power supply negative input.
2
B+
1.0mm
2
DC power supply positive input.
3
SCR
0.5mm
2
CANBUS shielded wire, with single end earthed.
4
CAN(H)
A CANBUS port which communicate with
HMC9000 controller.
5
CAN(L)
6
120Ω Terminal Resistor
Short out 5 and 6 terminals if 120Ω terminal resistor
is needed.
7
MP1
-
0.5mm
2
Connect with speed sensor(shielded wire is
recommended). Speed sensor input (-), B- has been
connected in the controller.
8
+
9
MP2
-
0.5mm
2
10
+
11
MP3
-
0.5mm
2
12
+
13
AOUT1
COM1
0.5mm
2
4~20mA output common port
14
mAOUTPUT1
4~20mA output port
15
AOUT2
COM2
0.5mm
2
4~20mA output common port
16
mAOUTPUT2
4~20mA output port
17
AOUT3
COM3
0.5mm
2
4~20mA output common port
18
mAOUTPUT3
4~20mA output port
19
AOUT4
COM4
0.5mm
2
4~20mA output common port
20
mAOUTPUT4
Sensor terminal
21
CIN1
COM(B+)
0.5mm
2
4~20mA analog input.
B+ input (supply power for pressure transmitter)
22