5.2 SHUTDOWN ALARM
Shutdown types are as follows,
No.
Items
DET Range
Description
1
PTIN1~ PTIN8
High
From “Waiting for load”
delay to “Cooling” delay
When the controller detects the sensor shutdown
alarms, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed
on HMC9000 LCD.
2
MP1~MP3
High
Always active
3
CIN1 High
From “Waiting for load”
delay to “Cooling” delay
4
PTIN1~ PTIN8
Low
From “Waiting for load”
delay to “Cooling” delay
5
CIN1 Low
From “Waiting for load”
delay to “Cooling” delay
5.3 PARAMETER CONFIGURATION
AIN16-M-01 parameters can be set via HMC9000 controller or HMC9000 PC software; more details
please refer to specific instruction of HMC9000.
Parameter Configuration List
Parameter
Contents
Default
Module Enable
0:Enable
1:Disable
Disable
PTIN1~ PTIN8 and
CIN1 Set
Sensor types/ Alarm Speed /Range/ High Shutdown
Enable / High Shutdown Value / High Shutdown
Delay / Low Shutdown Enable / Low Shutdown Value
/ Low Shutdown Delay / High Warn Enable / High
Warn Value / High Return Value / High Warn Delay/
Low Warn Enable / Low Warn Value / Low Return
Value / Low Warn Delay
For more details please refer to the following chapter
MP1~MP3 Set
Sensor Enable/Teeth Number Set/ High Shutdown
Enable / High Shutdown Value / High Shutdown
Delay/ High Warn Enable / High Warn Value / High
Return Value / High Warn Delay
4~20mA Output Set
Output can be configured as relevant to the sensor