CMM366A-4G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL
Chinese trademark English trademark SmartGen — make your generator smart SmartGen Technology Co., Ltd. No.28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: +86-371-67988888/67981888/67992951 +86-371-67981000 (overseas) Fax: +86-371-67992952 Web: www.smartgen.com.cn/ www.smartgen.cn/ Email: sales@smartgen.cn All rights reserved.
CONTENT 1 OVERVIEW ................................................................................................................................................. 4 2 PERFORMANCE AND CHARACTERISTICS.............................................................................................. 4 3 SPECIFICATION ........................................................................................................................................ 5 4 PANEL AND TERMINAL DESCRIPTION ....................
1 OVERVIEW CMM366A-4G Cloud Monitoring Communication Module is 4G GPRS wireless network communication protocol switch module which can achieve genset (with SCI) connect to Internet. After logging into cloud server, module will receive corresponding genset controller communication protocol from cloud server. And the module gains genset data via RS485 port, USB port, LINK port or RS232 port.
3 SPECIFICATION Table 2 – Technical Data Items Contents Operating Voltage DC 8.0V~35.0V, continuous power supply. Power Consumption Standby: ≤2W Working: ≤5W Digital Input Digital Input, connect (B-) is active.
4 4.1 PANEL AND TERMINAL DESCRIPTION PANEL INDICATOR AND BUTTONS Fig.1 – CMM366A-4G Front Panel Diagram Table 3 – Indicators Description Icon Note POWER/ALARM Green LED Light: Power supply normal indicator; Red LED Light: Common alarm indicator. RS485(Red) Normally Extinguish: RS485 disabled; Normally Light: Communication fail; Blink: Communication normal. USB(Red) Normally Extinguish: USB(Host) disabled; Normally Light: Communication fail; Blink: Communication normal.
Internal Lamp test/Reset Key: Press it for 1s, all the LEDs are illuminated; press it for 10s, reset the module to default and all the LEDs blink for 3 times. NOTE: After reset the module, parameters need to be re-configured via PC software. Please operate cautiously. 4.2 GPRS Connect GPRS antenna to GPRS/4G port. Antenna: 50Ω/SMA female. 4.3 GPS GPS enabled, connect GPS antenna to CMM366A-4G.
4.5 RS485 Receive genset data information by connecting module RS485 port with Genset Controller RS485 port. If communication is abnormal, 120Ω terminal resistance is recommonded. One end of shield wire hangs in the air and the other one connects with SCR. Fig.4 – RS485 Connection 4.6 RS232 Receive genset data information by connecting module RS232 port with Genset Controller RS232 port. Fig.
4.7 LINK Receive genset data information by connecting module LINK port with Genset Controller LINK port. Fig.6 – LINK Connection 4.8 USB HOST Receive genset data information by connecting module A-type USB port (female port) with Genset Controller USB port via USB cable. Fig.7 – USB HOST Connection 4.9 USB DEVICE All the parameters can be configured and view CMM366A-4G ID&Login password by connecting USB port with USB disk of PC software. Fig.
4.10 TERMINAL Table 4 – Terminals Description No. Function Cable Size 2 Note 1 B- 1.0mm Connected with negative of starter battery. 2 B+ 1.0mm2 Connected with positive of starter battery. 3A fuse is recommended. 3 Digital Input 1 1.0mm2 Active when connect to B-. Digital Input 2 1.0mm2 Active when connect to B-. 4 5 6 Relay Output 7 Normally Open 1.0mm2 Common 1.0mm2 Normally Close 1.0mm2 8 RS485 B(-) 0.5mm2 9 RS485 A(+) 0.5mm2 10 RS485 (SCR) 0.5mm2 11 RS232 RX 0.
5 PROGRAMMABLE PARAMETERS 5.1 CONTENTS AND SCOPES OF PARAMETERS Table 5 – Parameter Content & Scope No. Items Parameters Defaults Description Gateway 20 Chinese characters, letters or numbers 1 Site Name (0-65535) 2 URL (0-65535) www.monitoryun.com 3 Server Port (0-65535) 91 4 Security Code (0-65535) 123456 16 characters 1 GPS Enabled (0-1) 1 0: Manual Input 2 Longitude ((-180)-180)° 0.000000 3 Latitude ((-90)-90)° 0.000000 4 Altitude ((-9999.9)-9999.9)m 100.
Table 6 – Digital Input Ports Content No. Item Description 0 Not Used Not used. 1 Lamp Test All the indicators are illuminated when input is active. 2 Remote Control Inhibited Cloud start/stop control is prohibited when input is active. 3 Access Alarm Input Access alarm is uploaded to server when input is active. 4 Fire Alarm Input Fire alarm is uploaded to server when input is active. 5 Alarm Input External alarm is uploaded to server when input is active.
5.2 PC CONFIGURATION INTERFACE Connecting the USB port of CMM366A-4G communication module with PC USB port to configure the parameters. Fig.9 – Gateway Configuration Fig.
6 SYSTEM DIAGRAM One CMM366A-4G module connects with one genset monitor module. It can be connected via RS485 port, LINK port, RS232 port or USB port. Fig.
7 CASE DIMENSION AND INSTALLATION 2 ways for installation: 35mm guide rail in box or screw (M4) installation as below: Fig.12 – CMM366A-4G Case Dimension Fig.13 – CMM366A-4G Guide Rail Installation Fig.
8 FAULT FINDING Table 8 – Fault Finding Symptoms Possible Solutions Controller No Response for Power Check power voltage; Check controller connection wirings. GPRS/4G Indicator Not Light Check SIM card is inserted or not; Check GPRS antenna is connected or not. GPS Not Gain Location Check GPS parameters are enabled or not; Check GPS antenna is connected or not and placed outdoor or not. RS485 Comm.