Advanced 2 Stage Heating or Cooling Systems
TempLinc Zone does not have the ability to operate 1
st
or 2
nd
stages of Heat or Cool directly but can
instruct TempLinc Thermostat to operate the HVAC. 1
st
and 2
nd
stage of Heat or Cool engages under the
following conditions when TempLinc Thermostat is connected to the HVAC:
- TempLinc Zone Thermostat’s setpoint is set at 5 degrees or more below ambient in Cool
mode and 5 degrees or more above ambient in Heat mode
o i.e. Heat mode setpoint is 80°, ambient is 72° = 1
st
and 2
nd
stage engaged
o i.e. Cool mode setpoint is 78°, ambient is 84° = 1
st
and 2
nd
stage engaged
- TempLinc Zone Thermostat has been active in Heat or Cool for longer than 10 minutes
and did not reach setpoint
o i.e. Heat mode ran for 10 minutes and no change to ambient = 2
nd
stage engaged
o i.e. Cool mode ran for 10 minutes and no change to ambient = 2
nd
stage engaged
Note: It is possible for TempLinc Thermostat to occasionally engage and disengage 2
nd
stage during a
single Heating or Cooling cycle as variables are met
Factory Reset to Default
Factory Reset Changes
INSTEON is reset (all links removed)
Day / time is changed to 12:00, Monday
Programming times, temperatures and other settings are reset to their default value
Factory Reset Does Not Change
Temperature offset
Humidity Offset
F or C setting
Reset Option 1
5) Open TempLinc Zone Thermostat and remove a battery
6) Wait 10 seconds
7) While continuously holding the Set button ~10 seconds, re-insert the removed battery
Device will blink all segments and do continuous (Beep) during 10 seconds
8) When blinking / buzzing stops, release Set button
Device goes into factory reset for ~10 seconds and will perform a series of self tests.
Device will return to normal operations and display screen returns to normal
Reset Option 2
9) Press & hold TempLinc Zone Thermostat Set button until it beeps
TempLinc Zone Thermostat Set LED blinks GREEN
TempLinc Zone Thermostat will (Beep)
10) Press & hold TempLinc Zone Thermostat Set button again until it beeps
TempLinc Zone Thermostat Set LED blinks RED
TempLinc Zone Thermostat will (Beep)
LCD display indicates the group that you are unlinking from (default is cooling)
11) Double tap the Set button
12) Press and hold the set button again for ~10 seconds
Device will blink all segments and do continuous (Beep) during 10 seconds
13) When blinking / buzzing stops, release Set button
Device goes into factory reset for ~10 seconds and will perform a series of self tests.
Device will return to normal operations and display screen returns to normal