Datasheet

Wiring with External Equipment
Connection
method
Model
NPN transistor output
PNP transistor output
CEU5-
CEU5P-
However, the COM of the input circuit and the COM of the output circuit are electrically insulated
from each other.
Max. 30 VDC,
50 mA
Max. 30 VDC,
50 mA
CEU5 Control signal input
COM
1 k
2.2 k
or
(Select Reset/
Hold/Bank)
Power supply
(24 or 12 VDC)
Control signal
input
( )
<Wiring with multi counter CEU5>
1. Wiring of power source for driving counter
For power source for driving counter, use the one
with 90 to 264 VAC, 50/60 Hz or 21.6 to 264
VDC, 0.4 A or more.
2. Wiring for control signal input
(Selection among Reset, Hold, Bank)
Make each control signal to be the transistor
which can run more than 15 mA or the contact
output. Input time for reset signal should be more
than 10 ms. Bank selection and hold will function
only when the input signal is applied.
COM is common to each signal input. Applicable
to NPN and PNP input. Use 24 VDC or 12 VDC
for the power source of COM. Connect DC–
when PNP is applied, and DC+ when NPN is
applied.
3. Output circuit
There are two outputs, the NPN open collector and the PNP open collector.
The maximum rating is 30 VDC, 50 mA. Operating the controller by exceeding this voltage
and amperage could damage the electric circuit.
Therefore, the equipment to be connected must be below this rating.
Load
Load
Load
Load
Load
Load
Counter CEU5