User manual

5
Conversion Kit
1)
Check that the main gas supply line to the range is shut off and that the
power supply cord is disconnected.
2)
To adapt the regulator to the type of gas
used, the following must be done:
1 Unscrew the cover of the pressure
regulator.
2 Unscrew the spring retainer from the
cover.
3 Screw the spring retainer back on
according to the type of gas used (see
the following illustrations)
- Natural Gas: Set pressure to 4” W.C.P.
Incoming line pressure of 5” - 10 1/2”
W.C.P maximum;
- LP Gas: Set pressure to 11” W.C.P.
Incoming line pressure 12”- 13” W.C.P.
maximum.
The range must be isolated from the gas supply piping system by turning off the respective manual shut-
off valve during any pressure testing of the gas supply piping system at test pressures equal to or
greater than 1/2 PSIG (3.5 kPa).
Incoming line pressure upstream from the regulator must be 1” (2.5 cm) W.C.P. higher than the manifold
pressure in order to check the regulator.