setting interface of inverter.
Fig. 6-30 Anti-Reflux Setting of Inverter
Input status- input status: select “Input”;
Way to Control - control mode: select “Local”;
Reactive power type- reactive power type: select “Other” (no input).
Reactive local target: reactive power target: 0 (any value if no input is required);
Reactive remote target ID: reactive remote control: 0 (any value if no input is
required);
Active type- active power type: Select “Anti-reflux mode”.
Meritorious local goal- local target: This is the threshold for anti-reflux action,
0kW by default.
It is necessary to add the collection of electricity meter for anti-reflux function
and it can be judged on basis of the primary active power of electricity meter. The
incoming load is forward power, and PT/CT value should be taken into account
during electricity meter collection configuration, as shown in Section 6.5.6.
Active remote target ID- Active remote control ID: 0
Allocation strategy- allocation strategy: allocate in equal proportions;
Controlled Device Type ID- type ID of controlled device: 1 (inverter by default),
corresponding to the ID in the equipment type.
Click "Setting" and "Setup" buttons successively to start the device.