User Instructions

5EN
DIRIS Digiware M-50 & M-70 - 548751C - SOCOMEC
2. HAZARDS AND WARNINGS
The term "device" used in this document covers both DIRIS Digiware M-50 and M-70.
The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualied
professionals.
SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.
2.1. Risk of electrocution, burns or explosion
Caution: risk of electric shock Ref. ISO 7000-0434B (2004-01)
Caution: refer to the accompanying documentation each time this
symbol is shown
Ref. ISO 7000-0434B (2004-01)
Only duly authorised and qualied personnel may work or install/uninstall the device.
The instructions are valid together with the specic instructions for the device.
The device is designed only for its intended purpose as set out in the instructions.
Only accessories authorised or recommended by SOCOMEC may be used in association with the device.
Before proceeding with installation, maintenance, cleaning, disassembly, connection, or maintenance work, the
device and system must be cut off from the mains to avoid electrocution and damaging the system and device.
This device is not designed to be repaired by the user.
For any questions related to the disposal of the device, please contact SOCOMEC.
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc ash.
Ref. IEC 61010-2-032
Failure to comply with the instructions of the device and this safety information can cause bodily injury,
electric shock, burns, death or damage to property.
2.2. Risk of damaging the device
Caution: risk of electric shock Ref. ISO 7000-0434B (2004-01)
Caution: refer to the accompanying documentation each time this
symbol is shown
Ref. ISO 7010-W001 (2011-05)
To ensure that the device operates correctly, make sure that:
The device is correctly installed.
The auxiliary power supply voltage indicated on the device is observed: 24 VDC ± 10%.
A SOCOMEC 230 VAC / 24 VDC power supply unit (P15 ref. 4829 0120) or a 24 VDC max 20 W class 2 power
supply unit / SELV is used.
If a SOCOMEC power supply is not used, the device must be protected with a 1 A / 24 VDC fuse.
Only use RJ45 SOCOMEC cables to interconnect the modules via the Digiware bus. When the ambient
temperature exceeds +50°C, the minimum temperature rating of the copper cable to be connected to terminal
must be +85°C.
The device must not be cleaned.
The device must not be installed outdoor.
Failure to respect these precautions could cause damage to the device.