A list of properties denes each BACnet Object. Properties can be:
Required by the BACnet specication.
Optional. In this case, vendors can choose whether to implement them for their devices.
Proprietary. Vendors can add their own created properties.
Device Object:
Every BACnet device compatible with the DIRIS Digiware M-50 / M-70 must have the Device Object and its associated
required properties that fully describe the BACnet device to the network.
Example for the Device Object of the DIRIS Digiware M-50 / M-70.:
Property BACnet
Object_Identifier (OID) Required
Object_Name Required
Object_Type Required
System_Status Required
Vendor_Name Required
Vendor_Identifier Required
Model_Name Required
Firmware_Revision Required
Application_Software_
Version
Required
Protocol_Version Required
Protocol_Conformance_
Class
Required
Protocol_Services_
Supported
Required
Protocol_Object_Types_
Supported
Required
Object_List Required
Max_APDU_Length_
Supported
Required
Segmentation_Supported Required
APDU_Timeout Required
Location Optional
Description Optional
Local_Time Optional
Utc_Offset Optional
Local_Date Optional
Daylight_Saving_Status Optional
Active_COV_Subscriptions Optional
Serial_Number Optional
Property_List Optional
Version_Build_Date Proprietary
Operating_Hour_Counter Proprietary