16.4. BACnet IP conguration via Easycong System
The PICS le (Protocol Implementation Conformance Statement) is available at www.socomec.com
After logging in to Easy Cong System on the DIRIS Digiware M-50 / M-70, you can nd the BACnet IP settings in the
BACnet menu under BACnet settings:
Activation: Enable or disable the BACnet IP function
Main instance ID: 100 by default. It must be unique within the BACnet network.
Virtual network ID: Set the virtual network ID. It must be unique within the BACnet network.
The port used by the DIRIS Digiware M-50 / M-70 for BACnet IP communication is set to 47808 (BAC0 in hexadecimal)
and cannot be changed.