SA-12K Install Guide and Owner Manual
Table Of Contents
- Spec Sheet
- Wiring Diagrams
- GUI Screens
- Physical Installation
- Inverter Components
- Deciding Backup Circuits
- Single System Installs
- Mounting the Sol-Ark
- Integrating Batteries (Sol-Ark POWERED "OFF")
- E.M.P Systems Only
- Connecting Solar Panels
- Integrating a Generator
- Integrating Sensors and Accessory Placement
- Battery Temperature Sensor
- Limiter Sensors (CT Sensors)
- GEN Start Signal (Two-Wire)
- CANbus & RS485
- Wi-Fi Antenna (Dongle)
- Emergency Stop Signal & PV Rapid Shutdown Signal
- Misc. Hardware Recommendations
- Check the voltage on each PV input circuit
- Check Grid Input Voltage
- Check Battery Voltage
- Provide Power to Sol-Ark
- Indicator LED's
- Power Cycle Sequence
- Wi-Fi / Internet Connection
- Programming Guide
- Limiter Sensors (CT Sensors)
- Install Tips
- Batteries
- Parallel Systems
- Troubleshooting Guide
- LCD is not powering on
- Panels are connected, but DC Light is not on
- Panels are not producing
- Panels are not producing much power
- The system does not keep batteries charged
- Auto Gen-Start not working
- Normal LED isn't on
- The alarm light is on
- Grid HM value is negative when it should be positive (only applies in limited home mode)
- AC Overload Fault or Bus Unbalance Fault
- The system connects to grid and quickly disconnects
- DC Overload Fault
- System is beeping
- Battery cable sparks when connected
- Battery symbol on the home screen is red
- Battery symbol on the home screen is yellow
- Grid symbol on the home screen is yellow
- System has restarted
- Batteries were connected backward
- Why is the LCD screen still on when the power button is off?
- The Batt % meter is not reaching 100%
- Generator setup is reading 0Hz
- Color Touchscreen is Frozen
- Consant F18 Faults while powering loads within specification
- Troubleshooting Phasing Issues
- Sol-Ark 12K Error Codes
- Install Verification Checklist
- Sol-Ark 12K Limited Warranty
June 30
th
, 2022 50
Battery cable sparks when connected
• Put the built-in battery breaker in the off position before connecting or disconnecting batteries.
Battery symbol on the home screen is red
• The battery is under-Voltage or over-Voltage
Battery symbol on the home screen is yellow
• The battery is low, or the charge/discharge current is close to the programmed limit (which is ok)
Grid symbol on the home screen is yellow
• Grid parameters are out of specified range or grid is down
System has restarted
• It happens if the system is overloaded, battery voltage is greater than 63V, or Software update
Batteries were connected backward
• The battery breaker will trip. It can cause damage!
Why is the LCD screen still on when the power button is off?
• If PV or Grid power, LCD stays on, but the inverter and loads are off.
The Batt % meter is not reaching 100%
• The system needs to go through a small discharge/charge cycle first to calibrate the battery
Generator setup is reading 0Hz
• Select "General Standard" instead of UL1741. Then widen the frequency range to 55Hz-65Hz.
Color Touchscreen is Frozen
• Press and hold the escape button [] for 7-10 seconds
Consant F18 Faults while powering loads within specification
• Click the battery icon on the front of the inverter and look to see what the AC Output voltage is:
• If the AC Output Voltage is ~100V per leg (N/A in 220V single-phase grid mode), then check whether you are
missing a neutral connection, have a loose neutral wire, or have a damaged neutral wire somewhere in your AC
wiring.
• If the AC Output Voltage is ~120V per leg (N/A in 220V single-phase grid mode) and you have more than one
inverter in parallel, contact engineering support for further assistance.