15K Manual
Table Of Contents
- Spec Sheet
- Wiring Diagrams
- GUI Screens
- Physical Installation
- Inverter Components
- Deciding Backup Circuits
- Single System Installs (Whole-Home Backup)
- Mounting the Sol-Ark
- Integrating Batteries (Sol-Ark POWERED "OFF")
- Connecting Solar Panels
- Integrating a Generator
- Integrating Sensors and Accessory Placement
- Battery Temperature Sensor
- Limiter Sensors (CT Sensors)
- GEN Start Signal (Two-Wire)
- CANbus & RS485
- Wi-Fi Antenna (Dongles)
- Emergency Stop Signal & PV Rapid Shutdown Signal
- Misc. Hardware Recommendations
- Check the voltage on each PV input circuit
- Check Grid Input Voltage
- Check Battery Voltage
- Provide Power to Sol-Ark
- Indicator LED's
- Power Cycle Sequence
- Wi-Fi / Internet Connection
- Programming Guide
- Limiter Sensors (CT Sensors)
- Install Tips
- Batteries
- Parallel Systems
- Troubleshooting Guide
- LCD is not powering on
- Panels are connected, but DC Light is not on
- Panels are not producing
- Panels are not producing much power
- The system does not keep batteries charged
- Auto Gen-Start is not working
- Normal LED isn't on
- The alarm light is on
- Grid HM value is negative when it should be positive (only applies in limited home mode)
- AC Overload Fault or Bus Unbalance Fault
- The system connects to grid and quickly disconnects
- DC Overload Fault
- System is beeping
- Battery cable sparks when connected
- Battery symbol on the home screen is red
- Battery symbol on the home screen is yellow
- Grid symbol on the home screen is yellow
- System has restarted
- Batteries were connected backward
- Why is the LCD screen still on when the power button is off?
- The Batt % meter is not reaching 100%
- Generator setup is reading 0Hz
- Color Touchscreen is Frozen
- Consant F18 Faults while powering loads within specification
- Troubleshooting Phasing Issues
- Sol-Ark 15K Error Codes
- Install Verification Checklist
- Sol-Ark 15K Limited Warranty
June 30
th
, 2022 6
Sol-Ark 15K Torque Values Application Note
Load Terminal Block
62 IN Lbs
7 NM
Grid Terminal Block
62 IN Lbs
7 NM
Gen Terminal Block
62 IN Lbs
7 NM
Neutral / Ground Busbars
26.5 IN Lbs
3 NM
Cover Screws
26.5 IN Lbs
3 NM
Battery Connection
90.0 IN Lbs
10 NM
2” Minimum Horizontal Clearance || 6” Minimum Vertical Clearance
2”
2”
Temperature Derating
DC: 90C-100C Shutdown @ 100C
AC: 75C-82C Shutdown @ 82C
Do Not Use Impact Drivers to Tighten Any Fasteners on the Sol-Ark.