SA-15K Install Guide and Owner Manual
August 19
th
, 2022 50
Battery cable sparks when connected
• Put the built-in battery breaker in the off position before connecting or disconnecting batteries.
Battery symbol on the home screen is red
• The battery is under-Voltage or over-Voltage
Battery symbol on the home screen is yellow
The battery is low, or the charge/discharge current is close to the programmed limit (which is ok)
Grid symbol on the home screen is yellow
• Grid parameters are out of specified range or grid is down
System has restarted
• It happens if the system is overloaded, battery voltage is greater than 63V, or Software update
Batteries were connected backward
• The battery breaker will trip. It can cause damage!
Why is the LCD screen still on when the power button is off?
• If PV or Grid power, LCD stays on, but the inverter and loads are off.
The Batt % meter is not reaching 100%
• The system needs to go through a small discharge/charge cycle first to calibrate the battery
Generator setup is reading 0Hz
• Select "General Standard" instead of UL1741. Then widen the frequency range to 55Hz-65Hz.
Color Touchscreen is Frozen
• Press and hold the escape button [] for 7-10 seconds
Consant F18 Faults while powering loads within specification
• Click the battery icon on the front of the inverter and look to see what the AC Output voltage is:
• If the AC Output Voltage is ~100V per leg (N/A in 220V single-phase grid mode), then check whether you are
missing a neutral connection, have a loose neutral wire, or have a damaged neutral wire somewhere in your AC
wiring.
• If the AC Output Voltage is ~120V per leg (N/A in 220V single-phase grid mode) and you have more than one
inverter in parallel, contact engineering support for further assistance.