SA-15K Install Guide and Owner Manual

August 19
th
, 2022 50
Battery cable sparks when connected
Put the built-in battery breaker in the off position before connecting or disconnecting batteries.
Battery symbol on the home screen is red
The battery is under-Voltage or over-Voltage
Battery symbol on the home screen is yellow
The battery is low, or the charge/discharge current is close to the programmed limit (which is ok)
Grid symbol on the home screen is yellow
Grid parameters are out of specified range or grid is down
System has restarted
It happens if the system is overloaded, battery voltage is greater than 63V, or Software update
Batteries were connected backward
The battery breaker will trip. It can cause damage!
Why is the LCD screen still on when the power button is off?
If PV or Grid power, LCD stays on, but the inverter and loads are off.
The Batt % meter is not reaching 100%
The system needs to go through a small discharge/charge cycle first to calibrate the battery
Generator setup is reading 0Hz
Select "General Standard" instead of UL1741. Then widen the frequency range to 55Hz-65Hz.
Color Touchscreen is Frozen
Press and hold the escape button [] for 7-10 seconds
Consant F18 Faults while powering loads within specification
Click the battery icon on the front of the inverter and look to see what the AC Output voltage is:
If the AC Output Voltage is ~100V per leg (N/A in 220V single-phase grid mode), then check whether you are
missing a neutral connection, have a loose neutral wire, or have a damaged neutral wire somewhere in your AC
wiring.
If the AC Output Voltage is ~120V per leg (N/A in 220V single-phase grid mode) and you have more than one
inverter in parallel, contact engineering support for further assistance.