SA-15K Install Guide and Owner Manual
August 19
th
, 2022 6
Sol-Ark 15K Torque Values Application Note
Load Terminal Block
62 IN Lbs
7 NM
Grid Terminal Block
62 IN Lbs
7 NM
Gen Terminal Block
62 IN Lbs
7 NM
Neutral / Ground Busbars
26.5 IN Lbs
3 NM
Cover Screws
26.5 IN Lbs
3 NM
Battery Connection
90.0 IN Lbs
10 NM
2” Minimum Horizontal Clearance || 6” Minimum Vertical Clearance
2”
2”
Temperature Derating
DC: 90C-100C Shutdown @ 100C
AC: 75C-82C Shutdown @ 82C
Do Not Use Impact Drivers to Tighten Any Fasteners on the Sol-Ark.