Limiter Sensors (CT Sensors)
CT Sensors enable Limited to Home mode (meter zero) and Peak Shaving mode. CT sensors also allow the system to
calculate loads powered upstream of the Grid Breaker in the home.
CT Sensor Install Location
CT sensors should be installed on L1 and L2 (also L3 for parallel 3 phase) upstream of everything in the home
except for a Generator Transfer Switch, Knife Blade Disconnect or Bypass Transfer Switch (upstream of Main
Service Panel and Line-Side Tap see Diagrams Section Pgs. 8-16).
CT Sensor Size
Each inverter includes a pair of 5/8” CT sensors (fits up to 2/0 AWG service wires).
There are 15/16” (up to 4/0 AWG) and 2” sensors available for purchase if needed.
Dimensions refer only to CT sensor hole size, contact Sales at (972) 575-8875 Ext 1 to purchase larger sensors.
CT Sensor Wiring
CT sensor on L1 should be wired to pins 3 (white) and 4 (black).
CT sensor on L2 should be wired to pins 5 (white) and 6 (black).
White and black wires for each sensor should be twisted along length of run.
If needed, wires can be extended using Shielded Cat 6 (use both wires of twisted pair).
CT Sensor Direction
There is an arrow embossed on the CT sensor housing to determine direction.
Install pointing upstream to the service meter, EXCEPT in 3 phase installs where this
should be reversed.
Peak Shaving Mode
Grid Peak Shaving is available with the CT sensors in the location described above and applicable direction.
CT Ratio
Set the CT ratio; Default value is 2000/1. DO NOT change this value unless you speak with technical support, 3
rd
Party CT
sensors require our permission to not void warranty.
CT Sensor Extension Example