Table 11: UPS Specications
Parameters
Model
S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
Operating elevation Up to 10,000 ft. [3,000 m] at +40°C [+104°F] without derating
Storage elevation 50,000 ft. [15,000 m] max.
Audible noise
<43 dBA max. @
3 ft. [1 m] front &
sides; <46 dBA max.
@ 3 ft. [1 m] rear
<45 dBA max. @
3 ft. [1 m] front &
sides; <50 dBA max.
@ 3 ft. [1 m] rear
<46 dBA max. @
3 ft. [1 m] front &
sides; <45 dBA max.
@ 3 ft. [1 m] rear
<48 dBA max. @ 3 ft. [1 m] front & sides;
<48 dBA max. @ 3 ft. [1 m] rear
AGENCY
Safety UL1778, cUL Listed
RFI/EMI FCC Part 15, Class A = CISPR22 Class B
Surge immunity IEC62040-2 2
nd
Ed.
Transportation ISTA Procedure 1A
Table 12: Battery Cabinet Specications
Parameters
Model Number
S4K2U48BATC S4K2U96BATC
Used with UPS models S4K2U700C, S4K2U1000C, S4K2U1500C, S4K2U2000C S4K2U3000C
DIMENSIONS, D x W x H, in. [mm]
Unit 19.7 x 16.9 x 3.4 [497 x 430 x 85] 23.7 x 16.9 x 3.4 [602 x 430 x 85]
Shipping 24.3 x 22.4 x 10.3 [617 x 570 x 262] 28.2 x 22.4 x 10.3 [717 x 570 x 262]
WEIGHT, lb. [kg]
Unit 70.5 [32.0] 93.5 [42.4]
Shipping 77.2 [35.0] 101.4 [46.0]
BATTERY PARAMETERS
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 2 x 4 x 12 V x 9.0 Ah 2 x 6 x 12 V x 9.0 Ah
Battery mfr./Part number Panasonic/UP-RW1245; CSB/HR 1234W F2
Backup time See Table 13
ENVIRONMENTAL REQUIREMENTS
Operating temperature 0°C to +40°C [+32°F to +104°F]
Storage temperatures -15°C to +50°C [+19°F to +122°F] High ambient temperatures will reduce battery life
Relative humidity 0% to 95%, non-condensing
Operating elevation Up to 10,000 ft. [3,000 m] at +40°C [+104°F] without derating
Storage elevation 50,000 ft. [15,000 m] max.
AGENCY
Safety UL1778, cUL Listed
RFI/EMI FCC Part 15, Class A = CISPR22 Class B
Surge immunity IEC62040-2 2
nd
Ed.
Transportation ISTA Procedure 1A