Three Phase Inverters Design Guidelines (North America)
Background
The three phase inverters:SE14.4KUS, SE43.2KUS & SE33.3KUS, and three phase inverters with synergy technology: SE66.6KUS &
SE100KUS, differ in some of their design guidelines from other SolarEdge inverters. This document details these guidelines, which
should be followed in addition to all instructions in the SolarEdge Installation Guide.
Over-sizing
Inverter oversizing
PV inverters are designed so that generated output power will not exceed the maximum AC power. In many cases, oversizing the
inverter, i.e. having more DC power than the inverter AC power, may increase power output in lower light conditions, thus allowing
the installation of more DC power for a given inverter. DC/AC oversizing is defined as the ratio between the array STC power and
the inverter AC power.
The maximum DC/AC oversizing of all SolarEdge inverters, including the three phase inverters with synergy technology, is
135%.
Maintaining this limit ensures the lifetime of the inverter and is needed for keeping the inverter covered by its warranty. However,
the maximum oversizing is not necessarily the optimal oversizing. In many cases, you may design with lower sizing to ensure that
the inverter does not clip power. SolarEdge recommends performing proper simulations before oversizing the inverter. You may
refer to the Site Designer application to estimate the generated energy from the installation and the energy that may be lost due to
clipping.
For further details regarding inverter oversizing please refer to the document
Oversizing of SolarEdge Inverters.
String oversizing
The SE14.4KUS, SE43.2KUS and SE33.3KUS three phase inverters have three pairs of DC inputs and the three phase inverters with
synergy technology have three pairs of DC inputs per unit, allowing to connect up to 3 strings per unit without the need for an
external combiner box.
In order to reach 135% inverter oversizing without connecting more strings than inputs, these inverters support higher string power
subject to a few conditions. The table below summarizes the string power oversizing supported and the conditions required:
SE14.4KUS, 43.2KUS
SE33.3KUS, SE66.6KUS, SE100KUS
Number of strings connected per unit
3
3
Maximum power difference between the
strings
Up to 1,000W
Up to 2,000W
Power optimizer model
P600/P700/P730
P600/P700/P730
String oversizing
Up to 6,500W per string
Up to 15,000W per string
If the conditions specified above are not met, maximum string power is 6,000W for the SE14.4KUS & 43.2KUS, and 12,750W for the
SE33.3KUS, SE66.6KUS & SE100KUS.
When connecting these inverters with P800 power optimizer models, the regular over sizing is higher, therefor there is no extended
oversizing.