Energy Meter SE-MTR240-NN-S-S1 Specifications

©SolarEdgeTechnologies,Inc.Allrightsreserved.SOLAREDGE,theSolarEdgelogo,OPTIMIZEDBYSOLAREDGEaretrademarksorregi󰏭eredtrademarksofSolarEdgeTechnologies,Inc.
Allothertrademarksmentionedhereinaretrademarksoftheirrespectiveowners.Date:02/2019/V01/ENGNAM.Subjecttochangewithoutnotice.
SUPPORTED INVERTERS SINGLE PHASE INVERTERS UNITS
ELECTRICAL SERVICE
AC Input Voltage (Nominal) 240 Vac
AC Frequency (Nominal) 60 Hz
Max AC Input Current 100 mA
Connector Type Terminal block - 22 to 12 AWG
Grids supported
L1 / L2 / N / PE
L1 / L2 / PE
Power Consumption (Nominal) 3 W
METER ACCURACY
(
@ 77°F / 25°C, PF:0.7
-
1
)
1 - 100% of Rated Current CT ±1.0 %
CURRENT TRANSFORMERS
(
1
)
Nominal Input (at CT Rated Current) CT1, CT2: 0.333 Vac RMS
Rated RMS current
(2)
200 400 A
Dimensions (Internal / External) 0.8 x 0.8; 2.4 x 2.4 / 20 x 20; 61 x 61 1.26 x 1.83; 3.3 x 4.5 / 32 x 46.5; 83.4 x 114 in/mm
STANDARD COMPLIANCE
Safety UL 1741:2010 Ed.2(Supplement SA)+R: 07 Sep 2016
Emmissions FCC 47 CFR Part 15 Subpart B
ENVIRONMENTAL
Operating Temperatures -40 to +140 / -40 to +60 °F / °C
Relative Humidity (noncondensing) 5-90 %
Enclosure type High impact, ABS and/or ABS/PC pla󰎯ic UL 94V-0, IEC FV-0
Protection Rating NEMA Type 3R
INSTALLATION SPECIFICATIONS
Dimensions (HxWxD) 8.1 x 12.4 x 4.6 / 206.6 x 316 x 117.5 in / mm
Weight 3.9 / 1.8 lb / kg
Conduit Entry Diameters 0.75 or 1 / 19 or 25 in
Mounting Type Bracket mount
Energy Meter with Modbus Connection
for North America
SE-MTR240-NN-S-S1
* Current Transformers (CTs) should be ordered separately: SEACT0750-200NA-20 (200A); SEACT1250-400NA-20 (400A). Each comes in boxes of 20.
(1)
Current Transformers should be ordered separately: SEACT0750-200NA-20 (200A) or SEACT1250-400NA-20 (400A), 20 per box
(2)
For other ratings contact SolarEdge
Current Transformer Dimensions
200ACT
400ACT
Connecting the Energy Meter
CT
CT
L1
L2
L2CT
L1CT
Ground
RS485
Meter
Connections
Neutral
L1 L2