Installation Guide Manual
Table Of Contents
- Disclaimers
- Support and Contact Information
- Revision History
- Contents
- HANDLING AND SAFETY INSTRUCTIONS
- IMPORTANT SAFETY INSTRUCTIONS
- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Mechanical Specifications
- Appendix C: External Fan Maintenance and Replacement
- Appendix D: Replacing and Adding System Components
- Appendix E: Determining the Circuit Breaker Size
- Technical Specifications - Single Phase Inverters (North America)
- Technical Specifications - Three Phase Inverters (North America)
When installing inverters one above the other, leave at least 8" (20 cm)
between the top of an inverter and the bottom of the Safety Switch.
When installing inverters side by side, follow these clearance
specifications:
Location
Indoor
Installation
Outdoor Installation
Locations where the
annual average high
temperature
(1)
is below
25˚C / 77˚F
20 cm / 8"
between
inverters
5 cm / 2" between inverters (if
inverters are also installed one
above the other, maintain the
indoor installation clearance)
Locations where the
annual average high
temperature
1
is above
25˚C / 77˚F
40 cm / 16"
between
inverters
(1)
Annual average high temperature – the average of the 12 monthly average highs, for
example:
Refer to http://www.weatherbase.com/ to find the value in your location.
-Three Phase System Installation Guide MAN-01-00002-4.3
38 Mounting the Inverter