String Sizing Info for Optimizers

March 2017
Application Note - SolarEdge String Sizing, North America
Introduction
There are two primary criteria for string sizing in a SolarEdge system. Maximum (STC) power per string, and minimum and maximum
string lengths. This document explains how these values are determined and provides the string sizing rules for the different inverter
and optimizer combinations. For additional system design information refer to the inverter and optimizer datasheets.
Sizing rules typically depend on the type of inverters and optimizers used:
Inverters: single phase or three phase
Optimizers: general or commercial
Commercial optimizers can be used only with three phase inverters, while general optimizers can be used with both single and three
phase inverters.
General optimizers typically have one PV module per optimizer, and commercial optimizers typically have two modules. However
these are not fixed requirements and as long as the cumulative power and voltage/current of the modules meets the optimizer
specifications as detailed in the datasheet, connecting additional modules per optimizer is permitted (for example connecting
2x120W modules in series to a single P300 general optimizer). Refer to the Connecting Multiple Modules to Power Optimizers
application note for details.
NOTE
In the context of this document, string length refers to the number of optimizers and modules in the string. When designing the
installation make sure to maintain the maximum physical string length as well: The total cable length of the string (including power
optimizers’ cables) should not exceed 1000ft./300m from DC+ to DC- of the inverter (2,300ft./700m when using the SE14.4KUS and
SE33.3KUS inverters).
Maximum String Power
Maximum string power is simply the “Inverter Nominal DC Input Voltage” multiplied by the “Optimizer Maximum Output Current”.
These values can be found on the inverter and optimizer datasheets respectively. Table 1 details the values of available products.
Inverter Model
AC Grid Voltage
[V]
Inverter Nominal DC
Input Voltage [V]
Optimizer Max
Output Current [A]
Maximum String
Power [Wp]
Single phase inverters
SE3000A-US SE11400A-US
240
350
15
5,250
Single phase HD-Wave
Inverters SE3000H-US
SE6000H-US
240
380
15
5,700
Single phase HD-Wave Inverter
SE7600H-US
240
400
15
6000
SE9KUS, SE14.4KUS
120/208
400
15
6000 (or 6500 in
some cases
1
)
18 (P800)
7200
SE10KUS, SE20KUS, SE33.3KUS
277/480
850
15
12750 (or 15000 in
some cases
2
)
18 (P800)
15300
Table 1: Maximum string power
1
For SE14.4KUS only, when used with P600/P700/P730, it is allowed to install up to 6500W per string when 3 strings are connected
to the inverter and when the maximum power difference between the strings is up to 1000W.
2
For SE33.3KUS only, when used with P600/P700/P730, it is allowed to install up to 15000W per string when 3 strings are connected
to the inverter and when the maximum power difference between the strings is up to 2000W.