Installation Guide

Verifying Meter Connection using SetApp
1. From the SetApp main menu, select Status.
2. In the Communications section of the Status page, check the value of the RS485-x
field, which lists:
The connection protocol (for example, Modbus, SE Master, SE Slave)
"x of y", where x is the number of meters configured, and y is the number of
meters connected.
Verifying Meter Connection Using the Device Display
1. Press the Enter button or the LCD external button until the Communication status
screen is displayed as shown below. When two meters are connected, a screen
similar to the following should appear:
D e v P r o t # #
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
R S 4 8 5 - 2 < - - - > < - - > < - - >
Z i g B e e < - - - > < - - > < - - >
Dev: The type of device configured to this port. MLTindicates multiple meters.
Prot: The number of configured meters. For dual meters, it should display "02". If
not, refer to
Troubleshooting
below.
## : The number of communicating meters. For dual meters, it should display "02". If
not, refer to
Troubleshooting
below.
2.
Press the Enter button or the LCD external button until reaching the Meter status
screen showing the total energy [Wh]. There is a status screen for each meter
function. For example, for an export+import meter and a production meter, there
will be three status screens: for export, import and production. The following is an
example of an export meter:
E x p o r t M e t e r
S t a t u s : < O K >
< E r r o r M e s s a g e >
T o t a l [ W h ] : X X X X X X X
Status: Displays OK if the meter is communicating with the communication board.
<Error message>: If an internal meter error occurs, it will be displayed here. Refer to
Troubleshooting the Meter
on page 29.
Total [Wh]: The amount of Watts per hour of the designated meter.
Energy Meter with Modbus Connection MAN-01-00270-1.3
38 Verifying the Meter Connection