Installation Manual

Appendix B: Technical Specifications
Single Phase 3-7.6kW Inverters
SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US Units
OUTPUT
Nominal AC power output 3000 3800 5000 6000 7600 VA
Maximum AC power output 3300 4150
5400 @208
5450 @240
6000 8350 VA
AC Output Voltage Min.-Nom.-Max.
1
183-208-229 Vac
- - + - -
AC Output Voltage Min.-Nom.-Max.
1
211-240-264 Vac
+ + + + +
AC frequency min-nom-max
1
59.3 60 60.5 (with HI country setting: 57 60 60.5) Hz
Max. output fault current and duration @208V --- --- 26 / 20 --- --- A / ms
Max. output fault current and duration @240V 14 / 20 17.5 / 20 23 / 20 27.5 / 20 40 / 20 A / ms
Max. continuous output current 12.5 16
24 @208V
21 @240V
25 32 A
Max. output overcurrent protection 40 A
Power factor range 1 (adjustable from -0.95 to +0.95)
GFDI threshold 1 A
Total harmonic distortion <3%
1
For other regional settings, please contact SolarEdge support.
Appendix B: Technical Specifications
SolarEdge-Installation Guide MAN-01-00002-4.0