Installation Manual

WARNING!
The inverter must be configured to the proper country in order to ensure that it
complies with the country grid code and functions properly with that country grids.
L'onduleur doit être configuré pour le pays approprafin d'assurer un
fonctionnement convenable avec le réseau de ce pays.
Alistofcountriesisdisplayed.Ifnocountryisconfigured,thevalueis<NONE>.
NOTE
If an inverter is not configured to any country, it will not produce energy, and the
following message will be displayed on the LCD:
No Country Selected
Aplussign(+)nearthecountryindicatesthatanothermenuwillbedisplayedafter
selection.
l WhenselectingAuto(singlephaseonly),theinverterautomaticallydetectsthe
usedgrid:208VACor240VAC.Whenusingsinglephaseinverters,referto
Supported AC Gridsonpage11todetermineiftheAutooptionmaybeused.
l WhenselectinganoptionwithNo NeutralorNo N,connectiontoNeutrallineis
notrequired.Foranyotheroption,youmustconnecttheNeutralline.
l Whenconnectingtothe480/277Vgrid,selectthe277Vsetting.
2. Confirmyourcountryselectionintheconfirmationscreen:ToggletoYES andpressEnter.
Language
1. SelecttheLanguage optiontosetthelanguageinwhichtheLCDshoulddisplay.
2. Confirmyourlanguageselectionintheconfirmationscreen:ToggletoYESandpress
Enter.
Communication
1. SelecttheCommunication optiontodefineandconfigure:
l Thecommunicationoptionusedbytheinvertertocommunicatewiththe
SolarEdgemonitoringportal
l ThecommunicationoptionusedtocommunicatebetweenmultipleSolarEdge
devicesorotherexternalnon-SolarEdgedevices,suchaselectricitymetersor
loggers.
SolarEdge-Installation Guide MAN-01-00002-4.0
58