Creating an Ethernet (LAN) Connection
ThiscommunicationoptionenablesusinganEthernetconnectiontoconnecttheinvertertothe
monitoringplatformthroughaLAN.
Figure 25: Example of Ethernet connection
Ethernetcablespecifications:
l Cabletype–ashieldedEthernetcable(Cat5/5ESTP)maybeused
l Maximumdistancebetweentheinverterandtherouter–100m/330ft.
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices.
For details refer to: https://www.solaredge.com/sites/default/files/overvoltage_
surge_protection_na.pdf.