Step 3: Verifying Proper Activation
Afterthewake-uptimeisover,astatusscreensimilartothefollowingappearsontheinverterLCDpanel:
V a c [ V ] V d c [ V ] P a c [ W ]
2 4 0 . 7 3 7 1 . 9 2 3 4 9 . 3
P _ O K : X X X / Y Y Y < S _ O K >
. . . . . . . . . . . . . . . . . O N
1. Verifythefollowing:
l ThegreeninverterLEDissteadilylit.
l TheON/OFFindicatorontheLCDpanelreadsON.
l P_OK: XXX/YYY:Thereisaconnectiontothepoweroptimizersandatleastonepoweroptimizeris
sendingmonitoringdata.Optimizerssendtelemetriesinafrequencyofupto10minutes.
l S_OK appears,iftheinverterisconnectedtotheSolarEdgemonitoringplatform.
l Vac [V]specifiesthemeasuredgridACoutputvoltage.
l Vdc [v] :SpecifiestheDCinputvoltage,whichshouldequalthesumoftheoutputvoltagesofall
modules(andshouldbewithintheoperatingrangeoftheinverter).
l Pac [W]specifiestheACoutputpowerproduced.
2. Takenoteoftheserial#ontheinverterlabelusingthedetachable2Dbarcodestickeroneachdevice.
ThisinformationisusedintheSolarEdgemonitoringplatformtoidentifythisinverterandisneeded
toopenanewsiteinthemonitoringplatform.
YourSolarEdgepowerharvestingsystemisnowoperational.
Step 4: Reporting and Monitoring Installation Data
NOTE
This step requires connecting one of the communication options. Refer to Setting Up
Communication to the Monitoring Platform on page 69.
The SolarEdge Monitoring System
TheSolarEdgecloud-basedmonitoringplatform(monitoringplatform)enablesaccessing
SolarEdgesiteinformation,includingup-to-dateinformationviewedinaphysicalor
logicalview.ThemonitoringplatformisdescribedindetailintheSolarEdgeMonitoring
PlatformUserGuide,availableontheSolarEdgewebsiteat
http://www.solaredge.us/files/pdfs/solaredge-monitoring-platform-user-guide.pdf.The
SolarEdgemonitoringplatformcandisplaylogicalandphysicallayoutsoftheinstalled
system,asfollows:
l Logical Layout:Showsaschematiclogicallayoutofthecomponentsinthesystem,suchas:inverters,
stringsandmodules,aswellastheirelectricalconnectivity.Thisviewenablesyoutoseewhich
modulesareconnectedineachstring,whichstringsareconnectedtoeachinverter,andsoon.
l Physical Layout:Showsaschematicphysicallayoutofthecomponentsinthesystem,suchas:
inverters,stringsandmodules,aswellastheirelectricalconnectivity.Thisviewenablesabirdseye
viewoftheactuallocationofasystemcomponent.
Chapter 6: Commissioning the Installation
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
49