Installation Manual

10.
TerminatethefirstandlastSolarEdgedevice(inverter/Controlandcommunicationgateway,etc.)in
thechainbyswitchingaterminationDIP-switchinsidetheinvertertoON(movetheswitchup).The
switchislocatedonthecommunicationboardandismarkedSW7.
Figure 40: RS485 termination switch
NOTE
Only the first and last SolarEdge devices in the chain should be terminated. The other inverters in
the chain should have the termination switch OFF (down position).
Verifying the Connection
Afterconnectingandconfiguringacommunicationoption,performthefollowingstepstocheckthat
theconnectiontothemonitoringserverhasbeensuccessfullyestablished.
1. Closetheinvertercover:Attachtheinvertercoverandsecureitbytighteningthescrewswitha
torqueof9.0N*m/6.6lb.*ft.Forpropersealing,firsttightenthecornerscrewsandthenthetwo
centralscrews.
2. TurnONtheACtotheinverterbyturningONthecircuitbreakeronthemaindistributionpaneland
turningontheStorEdgeConnectionUnit.
3. WaitfortheinvertertoconnecttotheSolarEdgemonitoringplatform.Thismaytakeuptotwo
minutes.
AstatusscreensimilartothefollowingappearsontheLCDpanel:
V a c [ V ] V d c [ V ] P a c [ w ]
2 4 0 . 7 1 4 . 1 0 . 0
P _ O K : 0 0 0 / 0 0 0 < S _ O K >
- - - - - - - - - - - - - - - O F F
S_OK:IndicatesthattheconnectiontotheSolarEdgemonitoringplatformissuccessful.IfS_OKisnot
displayed,referto"Troubleshooting"onpage87.
Chapter 8: Setting Up Communication to the Monitoring Platform
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
77