Installation Guide

SE3000A-US SE3800A-US SE5000A-US SE6000A-US SE7600A-US Units
Cooling Natural Convection
Natural
convection
and internal
fan (user
replaceable)
Noise (typical) <25 <50 dBA
Minimum and maximum operating
temperature range
1
-13 to +140 / -25 to +60 (-40 to +60 version available
2
) ˚FC
Storage temperature range -13 to +140/ -25 to +60 ˚FC
Protection rating
RecommendedOCPDsizepergrid(youmayusealargersizethanthatrecommendedbutneverabove40A):
Inverter 208 VAC 240 VAC
SE3000A-US --- 20 A
SE3800A-US --- 20 A
SE5000A-US 30 A 30 A
SE6000A-US --- 35 A or 40 A
SE7600-US --- 40 A
1
SolarEdge’s 5kW and 6kW inverters operate at full power and full currents up to a temperature of 120°F/50°C. The inverters may be used above this temperature with reduced
ratings. For more information, refer to http://www.solaredge.com/files/pdfs/se-temperature-derating-note-na.pdf.
2
-40 version P/N: SExxxxA-US000NNU4 (for SE76000 inverter: SE7600A-US002NNU4)
Single Phase 3-7.6kW Inverters
SolarEdge-Installation Guide MAN-01-00002-4.0
100
NEMA 3R