RecommendedOCPDsizepergrid(youmayusealargersizethanthatrecommendedbutneverabove60A):
Inverter 208 VAC 240 VAC
SE10000-US 60 A 60 A
SE11400-US --- 60 A
Three Phase Inverters
SE9KUS SE10KUS SE20KUS Units
OUTPUT
Rated AC power output 9000 10000 20000 VA
Maximum AC power output 9000 10000 20000 VA
AC Output Line Connections
4-wire WYE (L1-L2-L3-N)
plus PE or 3 wire Delta
4-wire WYE (L1-L2-L3-
N) plus PE
4-wire WYE (L1-L2-L3-
N) plus PE
AC output voltage minimum-nominal-maximum (L-N)
1
105-120-132.5 244-277-305 244-277-305 Vac
AC output voltage minimum-nominal-maximum (L-L)
1
183-208-229 422.5-480-529 422.5-480-529 Vac
AC frequency min-nom-max
1
59.3 - 60 - 60.5
(with HI country setting 57 - 60 - 60.5)
Hz
Max. continuous output current (per Phase) 25 12 24 A
Max. output fault current and duration 26 / 20 12 / 20 24 / 20 A / mS
Max. back-feed current 0 A
Power factor range 1 (adjustable from -0.8 to +0.8)
GFDI threshold 1 A
1