Installation Guide

SE9KUS SE10KUS SE20KUS Units
Total harmonic distortion <3%
Utility monitoring, islanding protection, country
configurable set points
Yes
INPUT
Maximum DC power 12150 13500 27000 W
Transformer-less, ungrounded Yes
Maximum input voltage DC to Gnd 250 490 490 Vdc
Maximum input voltage DC+ to DC- 500 980 980 Vdc
Nominal input voltage DC to Gnd 200 425 425 Vdc
Nominal input voltage DC+ to DC- 400 850 850 Vdc
Maximum input current
1
26.5 13.5 26.5 Adc
Maximum short circuit current Adc
Reverse-polarity protection Yes
Ground-fault isolation detection 1MΩ Sensitivity
Maximum inverter efficiency 97.1 98.2 98.1 %
CEC weighted efficiency 96.5 98 98 %
Night-time power consumption <3 < 3 <3 W
ADDITIONAL FEATURES
Supported communication interfaces RS485, Ethernet, ZigBee (optional)
Rapid Shutdown NEC 2014 690.12 With SolarEdge rapid shutdown kit installed
2
1
A higher current source may be used; the inverter will limit its input current to the values stated.
2
Rapid shutdown kit P/N: Contact SolarEdge Support..
Appendix B: Technical Specifications
SolarEdge-Installation Guide MAN-01-00002-4.0
105