Installation Guide

Chapter 3: Installing the Inverter
Installtheinvertereitherbeforeorafterthemodulesandpoweroptimizershavebeen
installed.
NOTE
For single-phase 3-7.6kW inverters, use only copper conductors rated for a minimum of
75°C/167°F.
For single phase 10-11.4kW inverters and for three-phase inverters, use only copper
conductors rated for a minimum of 90°C/194°F.
For three-phase inverters where opposite polarity DC conductors are routed in the same
conduit, 1000V rated cables and components must be used.
Inverter Package Contents
l OneSolarEdgeinverter
l Onemountingbracket
l TwoAllenscrewsforfasteningtheinvertertothemountingbracket
l Thisinstallationguide
l Quickinstallationguide
l Inverteractivationinstructions(mayincludeanactivationcard)
Identifying the Inverter
RefertothestickerontheinverterthatspecifiesitsSerial NumberanditsElectrical Ratings.
ProvidetheserialnumberwhencontactingSolarEdgesupport.Theserialnumberisalso
requiredwhenopeninganewsiteintheSolarEdgemonitoringportal.
Inthefollowingsections,unlessotherwiseindicated,instructionsapplytobothsingle-phase
andthree-phaseinverters,thoughonlyonegraphicalexamplemaybepresented.
Figure 9: Single phase and three phase inverters
SolarEdge-Installation Guide MAN-01-00002-4.0
24
Chapter 3: Installing the Inverter