Installation Guide
9. TheinverterisconfiguredbydefaulttoLAN.Ifreconfigurationisrequired:
a. MakesuretheON/OFFswitchisOFF.
b. TurnONtheACtotheinverterbyturningONthecircuitbreakeronthemain
distributionpanel.
c. TurnONtheSafetySwitch.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the
inverter cover is removed.
RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le
couvercle de l'onduleur est retiré.
d. Usetheinternaluserbuttonstoconfiguretheconnection,asdescribedin
Communicationonpage58
NOTE
If your network has a firewall, you may need to configure it to enable the
connection to the following address:
l Destination Address: prod.solaredge.com
l TCP Port: 22222 (for incoming and outgoing data)
10. Verifytheconnection,asdescribedinVerifying the Connectiononpage82.
Creating an RS485 Bus Connection
TheRS485optionenablescreatingabusofconnectedinverters,consistingofupto31slave
invertersand1masterinverter.Usingthisoption,invertersareconnectedtoeachotherina
bus(chain),viatheirRS485connectors.Thefirstandlastinvertersinthechainmustbe
terminated.
RS485wiringspecifications:
l Cabletype:Min.3-wireshieldedtwistedpair(a4-wirecablemaybeused)
l Wirecross-sectionarea:0.2-1mm²/24-18AWG(aCAT5cablemaybeused)
l Maximumnodes:32
l Maximumdistancebetweenfirstandlastdevices:1km/3300ft.
NOTE
If using a cable longer than 10 m/33 ft in areas where there is a risk of induced voltage
surges by lightning, it is recommend to use external surge protection devices. For
details refer to: http://www.solaredge.us/files/pdfs/lightning_surge_protection.pdf. If
grounded metal conduit are used for routing the communication wires, there is no
need for a lightning protection device.