Installation Guide

9. TheinverterisconfiguredbydefaulttoLAN.Ifreconfigurationisrequired:
a. MakesuretheON/OFFswitchisOFF.
b. TurnONtheACtotheinverterbyturningONthecircuitbreakeronthemain
distributionpanel.
c. TurnONtheSafetySwitch.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the
inverter cover is removed.
RISQUE DÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le
couvercle de l'onduleur est retiré.
d. Usetheinternaluserbuttonstoconfiguretheconnection,asdescribedin
Communicationonpage58
NOTE
If your network has a firewall, you may need to configure it to enable the
connection to the following address:
l Destination Address: prod.solaredge.com
l TCP Port: 22222 (for incoming and outgoing data)
10. Verifytheconnection,asdescribedinVerifying the Connectiononpage82.
Creating an RS485 Bus Connection
TheRS485optionenablescreatingabusofconnectedinverters,consistingofupto31slave
invertersand1masterinverter.Usingthisoption,invertersareconnectedtoeachotherina
bus(chain),viatheirRS485connectors.Thefirstandlastinvertersinthechainmustbe
terminated.
RS485wiringspecifications:
l Cabletype:Min.3-wireshieldedtwistedpair(a4-wirecablemaybeused)
l Wirecross-sectionarea:0.2-1mm²/24-18AWG(aCAT5cablemaybeused)
l Maximumnodes:32
l Maximumdistancebetweenfirstandlastdevices:1km/3300ft.
NOTE
If using a cable longer than 10 m/33 ft in areas where there is a risk of induced voltage
surges by lightning, it is recommend to use external surge protection devices. For
details refer to: http://www.solaredge.us/files/pdfs/lightning_surge_protection.pdf. If
grounded metal conduit are used for routing the communication wires, there is no
need for a lightning protection device.
Chapter 7: Setting Up Communication
SolarEdge-Installation Guide MAN-01-00002-4.0
77