Installation Guide

Error # Single
Phase
Error # Three
Phase
LCD
Message
Description Troubleshooting
96/97/98 (Iac
L1/L2/L3 Max).
1/2/3
N/A 99-101
AC Voltage Too
High Line 1/2/3
Grid error.
Turn the inverter OFF and then ON. If this fault persists,
contact SolarEdge support.
N/A 105
Temperature
Too Low
Under temperature. If this fault persists, reinstall the inverter in a warmer place.
N/A 124
Ground Current
RCD
Internal hardware error. If this fault persists, contact SolarEdge support.
150, 151 150, 151
Arc Fault
Detected
An arc was detected on the DC side. Refer to Inverter Arc Detection and Interruption on page 123.
152 152
Arc detector
self-test failed
The arc detector is checked every time the inverter
starts up. The internal hardware that measures arcs
failed during wake-up tests.
Refer to Inverter Arc Detection and Interruption on page 123.
Appendix A: Errors and Troubleshooting
SolarEdge-Installation Guide MAN-01-00002-4.0
93