SPTL
Percent Timer Control-Lighted
For use with TR70/TR130/TR200/TR300
Operation
The Percent Timer Control-Lighted (SPTL) automatically turns on your TR70, TR130, TR200
or TR300 Total Recovery for All Climates unit every hour, ensuring proper ventilation for your
home around-the-clock. When the “Runtime %” light is on, the control is telling your Total
Recovery for All Climates unit to operate. Set the control and your ventilator will run once
every hour. How long it runs depends on the runtime percentage setting.
FOR CONSTANT OPERATION: Press the logo until the 100% light is on. The “Runtime %” light
turns on. The TR unit will run continuously.
FOR REGULAR OPERATION: Set the control at the percentage that is right for your home.
Press the logo until the light for the percent desired is on. See the "Percent Run Time Table"
for guidance. You may wish to adjust this percentage to your specific needs. For example, if
you have excess humidity in the winter, increase the ventilation percentage. You may also
want to decrease the ventilation percentage when the home will be unoccupied for many days,
or increase the ventilation percentage during a party.
F
OR NO REGULAR OPERATION: Press the logo until all lights are off. The control is off.
NOTE for TR systems with more than one control:
Another control may be causing your ventilator to run. If you wish to keep your ventilator from
running, check that none of your controls are calling for unit operation.
Installation
1. Install control in a standard 2" x 4" electrical box, with a minimum depth of 1.5", with the two
screws provided.
2. Wire Size: 18-22 gauge, no more than 500 feet. Wiring is non-polar.
3. The two wires from the TR should be attached to the ‘C’ and ‘R’ positions on the terminal
block on the back of the SPTL Control.
4. Use Lutron Decora™ cover plate to complete installation.
Percentage Run Time Table (to achieve 0.35 air changes per hour)
As recommended by the American Society of Heating, Refrigeration, and Air Conditioning Engineers
*Based on 8’ ceiling height. If ceiling is other than 8’, recalculate house volume based on your ceiling height.
Other standards and local codes should be considered when determining the required ventilation rate.
House Living
Area
House
Volume*
% Setting with % Setting with % Setting with % Setting with
(square feet) (cubic feet)
TR70@69 cfm TR130@124 cfm TR200@181 cfm TR300@295 cfm
750 6000 51% 28% 19% 12%
1250 10000 85% 47% 32% 20%
1750 14000 100% 66% 45% 28%
2250 18000 85% 58% 36%
2750 22000 100% 71% 44%
3250 26000 84% 51%
3750 30000 97% 59%
4250 34000 100% 67%
5125 41000 81%
5750 46000 91%
6500 52000 100%
Wiring
Diagram
FRONT
BACK
Use (1) SPTL and to (6) SPBL controls, wires in parallel.
SPTL Percent Time
r
SPBL
SPBL
To install one or more additional low-voltage controls
other than the SPTL or SPBL, install a 150 ohm resistor
(rated at 1/8 watt or more) between one terminal on the
ventilator and one of the wires to the other controls as
shown. (A 150 ohm 1/8 watt resistor is provided with a
SPTL.
)
Wire the other controls in
p
arallel with each other.