Specification Sheet

For more information contact us at www.solerpalau-usa.com or 1.800.961.7370 for additional submittal drawings.
Soler & Palau will not be responsible for fabrication changes or errors resulting from customer use of a non-current submittal drawing.
MODEL TR300
( E n e r g y R e c o v e r y Ve n t i l a t o r s ( E R V ) )
TR300_Submittal - 8.3.10
6393 Powers Avenue
Jacksonville, Florida 32217-2298
P: 800.961.7370 F: 800.961.7379
www.solerpalau-usa.com
LISTED
DUCTED HEAT
RECOVERY VENTILATOR
89S5
Blowers
34" Line Cord
Interlock Switch
Energy Transfer Core
Filters
24 Volt AC
Control
Terminal
Line Cord
RA
OA
FA
EA
23 7/8"
20 1/8"
41 1/2" Service Access
9 3/4"
10"
5 1/2"
5 1/2"
9 1/8"
5 1/2"
5 1/2"
9 1/8"
7 3/8"
8 3/4"
To Fit 8" Duct
FRONT VIEW
28 3/4"
TOP VIEW
RIGHT VIEW
Specications
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airow Range: 150-300 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.2 hp
V Hz Phase Input Watts FLA
120 60 Single 310 @ 293 CFM 3.3
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10-1/2” x 21-3/4” x 1”
Weight: 72 lbs (unit), 85 lbs (in carton)
Shipping Dimensions: 21-1/2” W x 32” L x 29” H
Options:
SPTL - Percentage Timer Control
SPBL - Push Button Point-of-Use Control
SFM Percentage Timer Control with Furnace Interlock
SHW-20 - Dehumidistat Control
Airow CFM ESP in H
2
O Temp EFF% Total EFF% Winter/Summer*
155 1.0 80 70/51
199 0.9 76 67/48
249 0.8 72 62/44
268 0.7 71 61/42
289 0.6 69 58/39
300 0.5 68 57/38
310 0.4 67 56/37
* Contact Factory for HVI certication report for complete certied rating.
Core Performance
EA: Exhaust Air to outdoors
OA: Outdoor Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
Dimensions

Summary of content (1 pages)