Specification Sheet

189
MODEL TXD
DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER
MODEL OVERVIEW
Model TXD direct drive fans are designed to exhaust air up to 3,400 CFM in high static pressure
applications to 1-1/4”. The aluminum exterior provides an attractive appearance. The non-overloading
backward inclined wheel with its higher static pressure capability makes this unit suitable for either
ducted or nonducted applications. Its roof or wall mounting permits location near the area to be
ventilated, allowing short duct runs and more efcient operation. Direct drive units use smaller diameter
wheels with lower rpm's, resulting in low sound levels and quiet operation. They have no belts or fan
bearings to maintain or adjust and consequently require very little maintenance.
Isolation of the motor from the air stream and the high velocity vertical (roof) or horizontal (wall) air discharge
make the Model TXD ideally suited for the removal of dirty, contaminated and/or high temperature air
from processes and buildings. Typical applications include restaurant hoods and similar kitchen exhaust
ventilation, fume and smoke removal, laboratory fume hood exhaust and chemical process exhaust.
MODEL NAME TYPICAL APPLICATIONS
TXD Removal of clean or contaminated air in general applications
TXDRHUL UL762 listed for grease removal
TXDW Wall mount version of TXD
TXDWRHUL UL762 version of TXDW
APPLICATION CONSTRUCTION OPTIONS
MODEL FEATURES
• Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4” w.g.
Attractive spun aluminum exterior
• Direct drive units have low sound levels and quiet operation
• Non-overloading backward inclined wheel for efciency at higher static pressures
• Roof or sidewall mounting options
AMCA Air and Sound Licensed
• cULus 705 or 762 Listed
All specications are subject to change without notice unless approved in submittal by S&P USA.
Industry best 5 year fan housing warranty, 1 year motor warranty
TXDRHUL units have 2 year fan housing warranty